background image

4 of 20

Sequence of Operation

Section A

General

Operation

Page 4 - 5

Section B

Mixing

Reset

Page 5 - 8

Section C

Boiler

Operation

Page 8 - 9

Section A —General Operation

POWERING UP THE CONTROL

When the GEO 360 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software 
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode.

OPERATION

The GEO 360 uses a floating action mixing valve to vary the supply water temperature to a wet heating system. The supply 
water temperature is based on either the current outdoor temperature, or a fixed setpoint.

Outdoor Reset

When the outdoor design (OUTDR DSGN) setting is not set to OFF, the GEO 360 
calculates a mixing supply water temperature based on the outdoor air temperature. 
The GEO 360 uses a 

Characterised Heating Curve

 and optionally indoor temperature 

feedback from an indoor sensor in this calculation.

Setpoint Control

When the outdoor design (OUTDR DSGN) setting is set to OFF, the GEO 360 
supplies a fixed mixing supply temperature equal to the MIX TARGET setting. An 
outdoor sensor is not required during this mode of operation.

FLOATING ACTION

A floating action actuator motor is connected to the GEO 360 on the 

Pwr Mix

Opn

, and 

Cls

 terminals (9, 10 and 11). The 

GEO 360 pulses the actuator motor open or close to maintain the correct mixed supply water temperature at the mix sensor 
when there is a mixing demand. The actuator is connected to a 4-way mixing valve. A visual indication as to whether the control 
is currently opening or closing the mixing valve is displayed in the LCD.

BOILER PROTECTION (BOIL MIN)

The GEO 360 is capable of providing boiler protection from cold 
mixing system return water temperatures. If the boiler sensor 
temperature is cooler than the BOIL MIN setting while the boiler 
is firing, the GEO 360 reduces the output to the mixing valve. This 
limits the amount of cool return water to the boiler and allows the 
boiler temperature to recover. This feature can only be used if a 
boiler sensor is installed.

EXERCISING

The GEO 360 has a built-in exercising function. If the system pump or valve has not been operated at least once every 3 days, 
the control turns on the output for a minimum of 10 seconds. This minimizes the possibility of a pump or valve seizing during a 
long period of inactivity. The GEO 360 ensures that the mixing valve operates over its entire range at least once each exercising 
period. While the control is exercising the 

Test

 LED flashes.

Note:

 The exercising function does not work if power to the control, pump, or valve is disconnected.

SETBACK (UNOCCUPIED)

To provide greater energy savings, the GEO 360 has a setback capability. With 
setback, the supply water temperature in the system is reduced when the building is 
unoccupied. By reducing the supply water temperature, air temperature in the space 
may be reduced even when the thermostat(s) are not turned down. Any time the 

UnO 

Sw

 (12) and the 

Com

 (13) terminals are shorted together, the control operates in the 

unoccupied (Night) mode. When in the unoccupied (Night) mode, the UNOCC segment 
is displayed in the LCD. The GEO 360 adjusts the supply water temperature based on 
the UNOCC settings made in the control. This feature has no effect when the control 
is used as a setpoint control.

Decreasing Outdoor Temperature

Incr

easing W

a

ter T

e

mperatur

e

Terminal Unit
(Heat Emitter)

Terminal Unit
(Heat Emitter)

Indoor Design

Indoor Design

Outdoor Design

Outdoor Design

Design Supply

Design Supply

Boiler Supply

Sensor

Mix Supply

Sensor

Boiler Return

Sensor

12

UnO

Sw

13

Com

Timer Switch

Содержание GEO360

Страница 1: ......

Страница 2: ...stal Display LCD to view system status and operating information Additional Functions Include Quick Setup for easy installation and programming of control User comfort adjustment to increase or decrea...

Страница 3: ...s alone for 20 seconds When the Item button is pressed and held in the VIEW menu the display scrolls through all the adjust items in both access levels Additional information can be gained by observin...

Страница 4: ...antial property damage if ignored Double insulated Local level appliances INSTALLATION CATEGORY II OCC UNOCC C F Pump Displays when the mixing system pump is in operation Burner Displays when the boil...

Страница 5: ...old mixing system return water temperatures If the boiler sensor temperature is cooler than the BOIL MIN setting while the boiler is firing the GEO 360 reduces the output to the mixing valve This limi...

Страница 6: ...connected to the Com and Indr terminals 16 and 18 In addition power must be applied to the Mixing Demand terminals 1 and 2 as described in the MIXING DEMAND section With the indoor sensor connected th...

Страница 7: ...n tube convector radiator and baseboard When a terminal unit heat emitter is selected the control automatically loads the design supply temperature MIX DSGN maximum supply temperature MIX MAX and mini...

Страница 8: ...MIX MAX setting and the MIX temperature is near the MIX MAX the MAX segment will be displayed in the LCD while either the MIX TARGET temperature or the MIX temperature is being viewed MIXING MINIMUM...

Страница 9: ...o improper cycling of the boiler because of inconsistent flow past the boiler supply sensor BOILER DIFFERENTIAL BOIL DIFF An on off heat source such as a boiler must be operated with a differential in...

Страница 10: ...result in damage to the equipment and possibly even personal injury It is your responsibility to ensure that this control is safely installed to all applicable codes and standards This electronic cont...

Страница 11: ...cording to the installation instructions in the GEO 360 Sensor Data Brochure and run the wiring back to the control Install the Mixing Sensor according to the installation instructions in the GEO 360...

Страница 12: ...nd side of the actuator power to the common terminal of the actuator Boiler Contact The Boiler terminals 7 and 8 are an isolated output in the GEO 360 There is no power available on these terminals fr...

Страница 13: ...ctrical test meter capable of reading from at least 0 300 V ac and at least 0 2 000 000 Ohms is essential to properly test the wiring and sensors Test The Sensors In order to test the sensors the actu...

Страница 14: ...ower to the circuit and remove the jumper Install a jumper between the Pwr Mix 9 and the Cls 11 terminals When the circuit is powered up the valve should move in the closing direction If it does not c...

Страница 15: ...ST menu by pressing and holding simultaneously for 1 second the Item and buttons The display will now show the word ADJUST in the top right corner The ROOM OCC adjustment is the first item displayed U...

Страница 16: ...Boiler sensor is present 10 to 130 C SETPOINT CONTROL Access the ADJUST menu by pressing and holding simultaneously for 1 second the Item and buttons The display will now show the word ADJUST in the...

Страница 17: ...ating system OUTDR DSGN OFF 1 Under oor Heating Screeded 2 Under oor Heating Plated 3 Fan Heater 4 Fin tube Convector 5 Radiator 6 Baseboard B3 The design indoor air temperature used in the heat loss...

Страница 18: ...s and relays are tested in the following test sequence TEST SEQUENCE Each step in the test sequence lasts 10 seconds During the test routine the test sequence may be paused by pressing the Test button...

Страница 19: ...priate in order to properly size configure and design that system and to ensure compliance with building and safety code requirements Outdoor Sensor S2 P1 Mix Sensor S3 Boiler Sensor S1 P2 C1 V1 T1 Z1...

Страница 20: ...able to read the boiler sensor due to a short circuit If the BOIL MIN adjustment is higher than 38 C the control closes the Boiler contact when the mixing valve starts to operate The boiler temperatur...

Страница 21: ...ions 170 H x 193 W x 72 D mm Approvals CE approved meets ICES FCC regulations for EMI RFI Ambient Conditions Indoor use only 0 to 39 C 90 RH non condensing Altitude 2000 m Installation Category II Pol...

Страница 22: ...of various risk levels or to important information concerning the life of the product Installation Outdoor Sensor 91629 STEP ONE GETTING READY Check the contents of this package If any of the contents...

Страница 23: ...e used or the wires can be run in a grounded metal conduit If using shielded cable one end of the shield should be connected to the Com terminal on the control and the other end should remain free The...

Страница 24: ...o install a draft barrier and or insulation behind the enclosure in order to prevent air from blowing through the wiring hole and affecting the sensor reading Surface Mounting For surface mounting mou...

Страница 25: ...an be placed alongside the one to be tested and the readings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from th...

Страница 26: ......

Отзывы: