15 of 20
View
Menu (1 of 1)
Display
Description
Range
Section
Installer
Ad
vanced
Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.
(OUTDR DSGN OFF)
-55 to 65°C
B1
Current room air temperature as measured by the indoor
sensor.
(Indoor Sensor is present)
-5 to 45°C
B3
Current mixed supply water temperature as measured by the
mixing sensor.
-10 to 130°C
B1
B2
B3
Target mixed supply is the temperature the control is currently
trying to maintain at the mixing sensor.
– – –, -10 to 130°C
Current boiler temperature as measured by the boiler sensor.
(Boiler sensor is present)
-10 to 130°C
SETPOINT CONTROL
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the
Item
, and buttons. The display will
now show the word ADJUST in the top right corner.
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Press and hold the
button until OFF is displayed.
Press and release the
Item
button to advance to the MIX TARGET adjustment. Use the or button
to select the desired temperature. The MIX TARGET setting is set to the desired setpoint supply
temperature.
Press and release the
Item
button to advance to the units adjustment. Use the or button to set
the scale to °C or °F.
To exit the ADJUST menu, press and release the Item button to advance to the ESC item. Then either
press the or button, or leave the buttons alone for 20 seconds.