16 of 20
Adjust
Menu (1 of 2)
Display
Description
Range
Section
Installer
Ad
vanced
Actual
Setting
B2
The desired room air temperature during an occupied
(Day) period.
(OUTDR DSGN OFF)
2 to 38°C
B2
The desired room air temperature during an
unoccupied (Night) period.
(OUTDR DSGN OFF)
2 to 38°C
B2
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
16 to 93°C
B2
The design outdoor air temperature used in the heat
loss calculation for the heating system. For setpoint
operation, set the OUTDR DSGN to OFF.
-51 to 0°C, OFF
B2
The type of terminal unit (heat emitter) that is being
used in the heating system.
(OUTDR DSGN OFF)
1
Underfl oor Heating
Screeded
2
Underfl oor Heating
Plated
3
Fan Heater
4
Fin-tube Convector
5
Radiator
6
Baseboard
B3
The design indoor air temperature used in the heat
loss calculation for the heating system.
(OUTDR DSGN OFF)
2 to 38°C
B3
The design supply water temperature used in the heat
loss calculation for the heating system.
(OUTDR DSGN OFF)
21 to 104°C
B3
The maximum supply water temperature for the
mixing system.
(OUTDR DSGN OFF)
26 to 100°C
A
The time that the actuating motor requires to operate
from fully closed to fully open.
30 to 230 seconds
(1 sec. increments)
B3
The minimum supply temperature for the mixing
system.
(OUTDR DSGN OFF)
OFF, 2 to 65°C
C1
The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)
OFF, 27 to 82°C