background image

5 of 20

FACTORY DEFAULTS

The control comes preset with several factory defaults. These defaults are based on the terminal unit (heat emitter) selection 
(see section B2). To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal 
unit (heat emitter) is changed, the terminal unit (heat emitter) number will flash when selected in the ADJUST menu.

To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while 
simultaneously holding the 

Item

 and   buttons. The terminal unit (heat emitter) number should now be displayed constantly in 

the LCD rather than flashing.

MIXING DEMAND

A mixing demand is required in order for the GEO 360 to provide heat. A mixing demand 
is generated by applying a voltage between 24 and 230 V (ac) across the 

Mixing 

Demand 

terminals (1 and 2). Once voltage is applied, the 

Mixing Demand

 pointer is 

displayed in the LCD. If the GEO 360 is not in Warm Weather Shut Down (WWSD), the 
GEO 360 closes the 

Sys Pmp

 contact. The GEO 360 calculates a MIX TARGET supply 

temperature based on the outdoor air temperature and settings. If required, the GEO 
360 operates the boiler in order to provide heat to the mixing valve.

SYSTEM PUMP OPERATION

 (SYS PMP)

The system pump contact (Sys Pmp, terminal 5) closes whenever there is a mixing demand and the GEO 360 is not in Warm 
Weather Shut Down (WWSD). The system pump segment is displayed in the LCD. After the mixing demand has been satisfied, 
the GEO 360 continues to operate the system pump for 20 seconds. This allows some residual heat to be purged out to the 
heating system. During WWSD, the system pump is operated based on the exercise function.

INDOOR SENSOR

An indoor sensor may be used in order to provide indoor temperature feedback. The indoor sensor is connected to the 

Com

 

and 

Indr

 terminals (16 and 18). In addition, power must be applied to the 

Mixing Demand

 terminals (1 and 2) as described in 

the MIXING DEMAND section. With the indoor sensor connected, the GEO 360 is able to sense the actual room temperature. 
Indoor temperature feedback fine-tunes the supply water temperature in the mixing system to maintain room temperature. To 
adjust the room temperature, use the ROOM OCC or ROOM UNOCC setting in the ADJUST menu at the control.

If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor 
should be located in an area which best represents the average air temperature of the zones.

CHARACTERISED HEATING CURVE

When used as a mixing reset control, the GEO 360 varies the supply water temperature based on the outdoor air temperature. 
The control takes into account the type of terminal unit (heat emitter) that the system is using. Since different types of terminal 
units (heat emitters) transfer heat to a space using different proportions of radiation, convection and conduction, the supply 
water temperature must be controlled differently. Once the control is told what type of terminal unit (heat emitter) is used, the 
control varies the supply water temperature according to the type of terminal unit (heat emitter). This improves the control of 
the air temperature in the building.

MIXING TARGET TEMPERATURE (MIX TARGET)

When used as a mixing reset control, the MIX TARGET temperature is calculated from the 

Characterised Heating Curve

 

settings, outdoor air temperature and optionally, indoor air temperature. When used as a setpoint control, the installer sets 
the MIX TARGET temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply 
temperature. If the control does not have a mixing demand,”– – –” is displayed as the MIX TARGET.

Section B: Mixing

Section B1: General

1 2

Mix

Demand

24 to 230 V (ac)

Section B1

General

Section B2

Installer

Section B3

Advanced

Содержание GEO360

Страница 1: ......

Страница 2: ...stal Display LCD to view system status and operating information Additional Functions Include Quick Setup for easy installation and programming of control User comfort adjustment to increase or decrea...

Страница 3: ...s alone for 20 seconds When the Item button is pressed and held in the VIEW menu the display scrolls through all the adjust items in both access levels Additional information can be gained by observin...

Страница 4: ...antial property damage if ignored Double insulated Local level appliances INSTALLATION CATEGORY II OCC UNOCC C F Pump Displays when the mixing system pump is in operation Burner Displays when the boil...

Страница 5: ...old mixing system return water temperatures If the boiler sensor temperature is cooler than the BOIL MIN setting while the boiler is firing the GEO 360 reduces the output to the mixing valve This limi...

Страница 6: ...connected to the Com and Indr terminals 16 and 18 In addition power must be applied to the Mixing Demand terminals 1 and 2 as described in the MIXING DEMAND section With the indoor sensor connected th...

Страница 7: ...n tube convector radiator and baseboard When a terminal unit heat emitter is selected the control automatically loads the design supply temperature MIX DSGN maximum supply temperature MIX MAX and mini...

Страница 8: ...MIX MAX setting and the MIX temperature is near the MIX MAX the MAX segment will be displayed in the LCD while either the MIX TARGET temperature or the MIX temperature is being viewed MIXING MINIMUM...

Страница 9: ...o improper cycling of the boiler because of inconsistent flow past the boiler supply sensor BOILER DIFFERENTIAL BOIL DIFF An on off heat source such as a boiler must be operated with a differential in...

Страница 10: ...result in damage to the equipment and possibly even personal injury It is your responsibility to ensure that this control is safely installed to all applicable codes and standards This electronic cont...

Страница 11: ...cording to the installation instructions in the GEO 360 Sensor Data Brochure and run the wiring back to the control Install the Mixing Sensor according to the installation instructions in the GEO 360...

Страница 12: ...nd side of the actuator power to the common terminal of the actuator Boiler Contact The Boiler terminals 7 and 8 are an isolated output in the GEO 360 There is no power available on these terminals fr...

Страница 13: ...ctrical test meter capable of reading from at least 0 300 V ac and at least 0 2 000 000 Ohms is essential to properly test the wiring and sensors Test The Sensors In order to test the sensors the actu...

Страница 14: ...ower to the circuit and remove the jumper Install a jumper between the Pwr Mix 9 and the Cls 11 terminals When the circuit is powered up the valve should move in the closing direction If it does not c...

Страница 15: ...ST menu by pressing and holding simultaneously for 1 second the Item and buttons The display will now show the word ADJUST in the top right corner The ROOM OCC adjustment is the first item displayed U...

Страница 16: ...Boiler sensor is present 10 to 130 C SETPOINT CONTROL Access the ADJUST menu by pressing and holding simultaneously for 1 second the Item and buttons The display will now show the word ADJUST in the...

Страница 17: ...ating system OUTDR DSGN OFF 1 Under oor Heating Screeded 2 Under oor Heating Plated 3 Fan Heater 4 Fin tube Convector 5 Radiator 6 Baseboard B3 The design indoor air temperature used in the heat loss...

Страница 18: ...s and relays are tested in the following test sequence TEST SEQUENCE Each step in the test sequence lasts 10 seconds During the test routine the test sequence may be paused by pressing the Test button...

Страница 19: ...priate in order to properly size configure and design that system and to ensure compliance with building and safety code requirements Outdoor Sensor S2 P1 Mix Sensor S3 Boiler Sensor S1 P2 C1 V1 T1 Z1...

Страница 20: ...able to read the boiler sensor due to a short circuit If the BOIL MIN adjustment is higher than 38 C the control closes the Boiler contact when the mixing valve starts to operate The boiler temperatur...

Страница 21: ...ions 170 H x 193 W x 72 D mm Approvals CE approved meets ICES FCC regulations for EMI RFI Ambient Conditions Indoor use only 0 to 39 C 90 RH non condensing Altitude 2000 m Installation Category II Pol...

Страница 22: ...of various risk levels or to important information concerning the life of the product Installation Outdoor Sensor 91629 STEP ONE GETTING READY Check the contents of this package If any of the contents...

Страница 23: ...e used or the wires can be run in a grounded metal conduit If using shielded cable one end of the shield should be connected to the Com terminal on the control and the other end should remain free The...

Страница 24: ...o install a draft barrier and or insulation behind the enclosure in order to prevent air from blowing through the wiring hole and affecting the sensor reading Surface Mounting For surface mounting mou...

Страница 25: ...an be placed alongside the one to be tested and the readings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from th...

Страница 26: ......

Отзывы: