Electro-pneumatic Control Panel Display Screens
Icon/Field
Icon/Field
Icon/Field
Description
Description
Description
Aux
Aux
Aux 1
1
1 Input
Input
Input
CM8281–11 Input Voltage Asserted: >16 VDC. Not Asserted: <5 VDC
Select input type:
• None: Not monitored.
• Start/Stop: See
• Ready Interlock: The system will Alarm if Not Asserted.
• Job Complete: The system will complete and log a job if Asserted, provided there has
been some amount of material dispensed.
Aux
Aux
Aux 2
2
2 Input
Input
Input
CM8281–21 Input Voltage Asserted: >16 VDC. Not Asserted: <5 VDC
Select input type:
• None: Not monitored.
• Start/Stop: See
• Ready Interlock: The system will Alarm if Not Asserted.
• Job Complete: The system will complete and log a job if Asserted, provided there has
been some amount of material dispensed.
Aux1
Aux1
Aux1 Output
Output
Output
CM8281–13 Output Voltage Asserted: 24 VDC. Not Asserted: 0 VDC
Select output type:
• None: Not monitored.
• System OK: Asserted while no Alarms are active.
• Pump Run: Asserted while the pumps are running.
• Sequence Complete: Asserted after an Automatic or Batching sequence has
completed.
• Container Low: Asserted when the system is below the “Container Low” point during
operation.
• Container Empty: Asserted when the system has emptied the container during
operation.
Aux2
Aux2
Aux2 Output
Output
Output
CM8281–23 Output Voltage Asserted: 24 VDC. Not Asserted: 0 VDC
Select output type:
• None: Not monitored.
• System OK: Asserted while no Alarms are active.
• Pump Run: Asserted while the pumps are running.
• Sequence Complete: Asserted after an Automatic or Batching sequence has
completed.
• Container Low: Asserted when the system is below the “Container Low” point during
operation.
• Container Empty: Asserted when the system has emptied the container during
operation.
Job
Job
Job Measurement
Measurement
Measurement
Delay
Delay
Delay
Delay after a batch is completed, during which the amount pumped is still recorded.
Default is 2 seconds, but may be set up to 5 seconds.
Current
Current
Current Scale
Scale
Scale Value
Value
Value
Displays the current read value from the scale.
* See
for more information.
** See
Setting Scale Feedback, page 51
for more information.
50
3A5402J