SS-CPC36-72
www.goodmanmfg.com
9
h
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, h
eat
m
ode
) — 5 t
ons
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage use voltage²
/ 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW &
BTU at 240V
Recommended
Airflow Range
Speed Tap
CPC060***1D***
42
60
EHK1-10
53 / 62
60 / 70
10
1750-2250 CFM
T3, T4, T5
EHK1-15
76 / 88
80 / 90
15
1750-2250 CFM
T3, T4, T5
EHK1-20
99 / 114
100 / 120
20
1850-2250 CFM
T5
CPC060***3D***
29
45
EHK3-10
34 / 40
35 / 45
10
1750-2250 CFM
T3, T4, T5
EHK3-15
47 / 55
50 / 60
15
1750-2250 CFM
T3, T4, T5
EHK3-20
60 / 70
70 / 70
20
1850-2250 CFM
T5
CPC060***3B***
25
40
---
EHK3-10
30 / 35
35 / 40
10
1750 - 2250 CFM
---
EHK3-15
43 / 50
45 / 50
15
1750 - 2250 CFM
---
EHK3-20
56 / 65
60 / 70
20
1850 - 2250 CFM
---
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW &
BTU at 480V
Recommended
Airflow Range
CPC060***4B***
12
20
EHK4-10
19
20
10
1750 - 2250 CFM
EHK4-15
25
25
15
1750 - 2250 CFM
EHK4-20
35
35
20
1850 - 2250 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW &
BTU at 575V
Recommended
Airflow Range
CPC060***7B***
10
15
EHK7-10
15
20
10
1750-2250 CFM
EHK7-15
22
25
15
1750-2250 CFM
EHK7-20
28
30
20
1850-2250 CFM
EHK7-25
34
35
25
---
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection Device
k
w C
orreCtion
f
aCtor
Minimum Airflow for Electric Heat
Heater Size
Minimum CFM
A Models
B Models
10
1,750
1,700
15
1,750
1,700
20
1,850
1,880