p
rodUCt
s
peCifiCations
p
rodUCt
s
peCifiCations
8 www.goodmanmfg.com
SS-CPC36-72
h
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, h
eat
m
ode
) — 4 t
ons
k
w C
orreCtion
f
aCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
Multiply rated kW by correction factor to get actual kW
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW &
BTU at 240V
Recommended
Airflow Range
CPC048***1D***
29
45
EHK1-10
48 / 56
50 / 60
10
1400-1800 CFM
EHK1-15
71 / 82
80 / 90
15
1575-1800 CFM
EHK1-18
84 / 97
90 / 100
18
1575-1800 CFM
CPC048***3D***
21
30
EHK3-10
29 / 34
35 / 35
10
1400-1800 CFM
EHK3-15
42 / 49
45 / 50
15
1575-1800 CFM
EHK3-18
50 / 58
60 / 60
18
1575-1800 CFM
CPC048***3B***
22
30
EHK3-10
30 / 35
35 / 35
10
1400-1800 CFM
EHK3-15
43 / 50
45 / 50
15
1575-1800 CFM
EHK3-18
51 / 59
60 / 60
18
1575-1800 CFM
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW &
BTU at 480V
Recommended
Airflow Range
CPC048***4B***
10
15
EHK4-10
17
20
10
1400-1800 CFM
EHK4-15
25
25
15
1575-1800 CFM
EHK4-18
29
30
18
1575-1800 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW & BTU
at 575V
Recommended
Airflow Range
CPC048***7B***
8
15
EHK7-10
15
20
10
1400-1800 CFM
EHK7-15
22
25
15
1575-1800 CFM
EHK7-18
25
30
18
1575-1800 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
Minimum Airflow for Electric Heat
Heater Size
Minimum CFM
A Models
B Models
10 kW
1,400
1,300
15 kW
1,575
1,400
18 kW
1,575
1,400