SS-CPC36-72
www.goodmanmfg.com
3
p
rodUCt
s
peCifiCations
— CpC036
CPC036
XXX1DXXXB
CPC036
XXX3DXXXB
CPC036
XXX3BXXXB
CPC036
XXX4BXXXB
CPC036
XXX7BXXXB
Cooling Capacity
Total BTU/h
34,600
34,600
34,600
34,600
34,600
Sensible BTU/h
25,600
25,600
25,600
25,600
25,600
SEER / EER
13 / 11.0
13 / 11.0
13 / 11.0
13 / 11.0
13 / 11.0
Decibels
78
78
78
78
78
ARI Reference #s
4385050
4385051
4385051
4385052
4397604
Evaporator Motor / Coil
Motor Type
Direct Drive
Direct Drive
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
1,200
1,200
1,200
1,200
1,200
Motor Speed Tap (Cooling)
Low Speed
Low Speed
---
---
---
Indoor motor FLA (Cooling)
2.50
2.50
3.8
1.9
2.3
Horsepower - RPM
⅓ - 890
⅓ - 890
1.0 - 1725
1.0 - 1725
1.5 - 1725
Piston Size (Cooling)
0.068
0.068
0.068
0.068
0.068
Filter Size (Qty)
(1) 24" x 24" x 2"
(1) 24" x 24" x 2"
(1) 24" x 24" x 2"
(1) 24" x 24" x 2"
(1) 24" x 24" x 2"
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge (oz.)
83
83
83
83
125
Evaporator Coil Face Area (ft²)
5.4
5.4
5.4
5.4
5.4
Rows Deep/ Fins per Inch
3 / 16
3 / 16
3 / 16
3 / 16
3 / 16
Evaporator Fan
Standard Direct Drive (D x W) HP
(10" X 9") ½
(10" X 9") ½
---
---
---
Standard Belt Drive (D x W) HP
---
---
(11" X 10") 1
(11" X 10") 1
(11" X 10") 1½
High-Static Belt Drive (D x W) HP
---
---
(11" X 10") 1½
(11" X 10") 1½
(11" X 10") 1½
# of Wheels (D x W)
---
---
1 (11" x 10")
1 (11" x 10")
1 (11" x 10")
Motor Sheave
---
---
1VL40 X ⅝
1VL40 X ⅝
1VL40 X ⅝
Blower Sheave / Belt
---
---
AK69 x 1 / AX55
AK69 x 1 / AX55
AK69 x 1 / AX55
Condenser Fan / Coil
Quantity of Condenser Fan Motors
1
1
1
1
1
Horsepower - RPM
¼ / 1,090
¼ / 1,090
¼ / 1,090
¼ - 890
¼ - 1,075
Fan Diameter/ # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
3,800
3,800
3,800
3,800
3,800
Face Area (ft²)
17.0
17.0
17.0
17.0
13.0
Rows Deep/ Fins per Inch
1 / 24
1 / 24
1 / 24
1 / 24
2 / 16
Compressor
Quantity / Type
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
Stage
Single
Single
Single
Single
Single
Compressor RLA / LRA
16.7 / 79.0
10.5 / 73.0
10.5 / 73.0
5.8 / 38.0
3.8 / 36.5
Electrical Data
Voltage-Phase-Frequency
208/230-1-60
208/230-3-60
208/230-3-60
460-3-60
575-3-60
Indoor Blower HP / FLA
⅓ / 2.5
⅓ / 2.5
1 / 3.8
1 / 1.9
1.5 / 2.3
Outdoor Fan HP / FLA
¼ / 1.4
¼ / 1.4
¼ / 1.4
¼ / 0.8
0.60
Total Unit Amps
20.57
14.35
15.65
8.47
6.68
Min. Circuit Ampacity¹
25
17
18
10
8
Max. Overcurrent Protection (amps)²
40
25
25
15
15
Power Supply Conduit Hole
1.125"
1.125"
1.125"
1.125"
1.125"
Low Voltage Conduit Hole
½"
½"
½"
½"
½"
Operating Weight (lbs)
500
500
500
500
500
Ship Weight (lbs)
525
525
525
525
525
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.