background image

p

rodUCt

 s

peCifiCations

p

rodUCt

 s

peCifiCations

28 www.goodmanmfg.com 

SS-CPC36-72

r

oof

 C

UrB

 i

nstallation

 — r

igging

Provisions for forks have been included in the unit base frame. No other fork 

locations are approved.
•  Unit must be lifted by the four lifting holes located at the base frame 

corners.

•  Lifting cables should be attached to the unit with shackles.
•  The distance between the crane hook and the top of the unit must not 

be less than 60”.

•  Two spreader  bars  must span  over  the  unit to prevent damage  to the 

cabinet  by  the  lift  cables.  Spreader  bars  must  be  of  sufficient  length 

so  that  cables  do  not  come  in  contact  with  the  unit  during  transport. 

Remove  wood  struts  mounted  beneath  unit  base  frame  before  set

-

ting  unit  on  roof  curb.  These  struts  are  intended  to  protect  unit  base 

frame  from  fork  lift  damage.  To  remove  the  struts,  extract  the  sheet 

metal  retainers  and  pull  the  struts  through  the  base  of  the  unit.  

Refer to rigging label on the unit.

Important:

 If using bottom discharge with roof curb, duct-work should be 

attached to the curb prior to installing the unit. Duct-work dimensions are 

shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions for proper curb installation. 

Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower 

than  the supply air end.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as 

a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care 

to center the unit. Check for proper alignment and orientation of supply and return openings with duct.
To assist in determining rigging requirements, unit weights are shown below.

C

orner

 & C

enter

-

of

-g

ravity

 l

oCations

30”

Compressor

Return

Evaporator Coil

Supply

Condenser

Coil

37”

Unit Weights

3-Ton 

Weights

4-Ton 

Weights

5-Ton 

Weights

6-Ton 

Weights

Corner Weight (A)

115

120

130

150

Corner Weight (B)

150

150

160

190

Corner Weight (C)

105

105

115

130

Corner Weight (D)

130

135

150

170

Unit Shipping Weight

525

540

580

665

Unit Operating Weight

500

515

555

640

Note: Weights are calculated without accessories installed.

Содержание CPC036XXX1DXXXB

Страница 1: ...ck with standard 2 filters Bottom utility entry AHRI Certified ETL Listed Cabinet Features Heavy gauge galvanized steel cabinet with UV resistant powder paint finish Full Perimeter Rail Cooling Capaci...

Страница 2: ...ns 400 400 000 BTU h 025 25 kW 075 75 kW X No Op ons A Down ow Economizer Voltage Supply Fan Drive Type Motors 1 208V 1 Phase 4 460V 3 Phase B Belt Drive 2 220 240V 1 Phase 50 Hz 5 380 415V 3 Phase 50...

Страница 3: ...10 1 of Wheels D x W 1 11 x 10 1 11 x 10 1 11 x 10 Motor Sheave 1VL40 X 1VL40 X 1VL40 X Blower Sheave Belt AK69 x 1 AX55 AK69 x 1 AX55 AK69 x 1 AX55 Condenser Fan Coil Quantity of Condenser Fan Motor...

Страница 4: ...x 10 1 11 x 10 Motor Sheave VL44 X 5 8 VL44 X 5 8 VL44 X 5 8 Blower Sheave Belt AK66 x 1 AX55 AK66 X 1 AK66 X 1 Condenser Fan Coil Quantity of Condenser Fan Motors 1 1 1 1 1 Horsepower RPM 1 090 1 09...

Страница 5: ...11 x 10 1 11 x 10 Motor Sheave VL44 x VL44 x VL44 x Blower Sheave Belt AK61x1 AX53 AK61x1 AX53 AK61x1 AX53 Condenser Fan Coil Horsepower RPM 1 090 1 090 1 090 1 090 1 075 Fan Diameter Fan Blades 22 4...

Страница 6: ...3 Condenser Fan Coil Quantity of Condenser Fan Motors 1 1 1 Horsepower RPM 1 075 1 075 1 075 Fan Diameter Fan Blades 22 4 22 4 22 4 Outdoor Nominal CFM 4 300 4 300 4 300 Face Area ft 18 7 18 7 18 7 Ro...

Страница 7: ...tual kW BTU at 240V Recommended Airflow Range CPC036 1D 25 40 EHK1 10 48 55 50 60 10 1250 1350 CFM EHK1 15 70 81 80 90 15 1400 1440 CFM CPC036 3D 17 25 EHK3 10 29 33 30 35 10 1250 1350 CFM EHK3 15 42...

Страница 8: ...M EHK1 15 71 82 80 90 15 1575 1800 CFM EHK1 18 84 97 90 100 18 1575 1800 CFM CPC048 3D 21 30 EHK3 10 29 34 35 35 10 1400 1800 CFM EHK3 15 42 49 45 50 15 1575 1800 CFM EHK3 18 50 58 60 60 18 1575 1800...

Страница 9: ...4 100 120 20 1850 2250 CFM T5 CPC060 3D 29 45 EHK3 10 34 40 35 45 10 1750 2250 CFM T3 T4 T5 EHK3 15 47 55 50 60 15 1750 2250 CFM T3 T4 T5 EHK3 20 60 70 70 70 20 1850 2250 CFM T5 CPC060 3B 25 40 EHK3 1...

Страница 10: ...8 240V MOP amps 208 240V Actual kW BTU 240V Recommended Airflow Range CPC072XXX3BXXX 31 45 EHK3 10 36 45 10 2 100 2 700 CFM EHK3 15 51 60 15 2 100 2 700 CFM EHK3 20 66 70 20 2 100 2 700 CFM EHK3 25 81...

Страница 11: ...7 1449 0 2 2 06 444 864 1476 0 1 2 08 446 866 Med 1396 0 3 2 02 432 891 1421 0 2 2 03 432 885 1335 0 4 1 97 418 916 1334 0 3 1 96 414 918 1273 0 5 1 91 404 940 1255 0 4 1 90 396 945 1153 0 6 1 83 380...

Страница 12: ...7 1 0 1611 0 56 1315 0 42 1011 0 28 1 2 1605 0 62 1299 0 46 976 0 31 1 4 1605 0 68 1281 0 51 959 0 35 1 6 1281 0 57 981 0 41 1 8 981 0 47 Standard Belt Drive Down Shot ESP W C Turns Open 0 1 2 3 4 5 C...

Страница 13: ...86 Med 1805 0 1 2 84 620 935 Med 1733 0 2 2 78 606 918 1704 0 2 2 71 590 967 1639 0 3 2 64 568 960 1625 0 3 2 59 558 990 1564 0 4 2 51 542 984 1549 0 4 2 47 540 1012 1434 0 5 2 35 508 1017 1437 0 5 2...

Страница 14: ...1559 0 64 1210 0 44 1 4 1888 0 92 1543 0 70 1195 0 49 1 6 1557 0 77 1180 0 54 1 8 1192 0 60 Standard Belt Drive Down Shot ESP W C 0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP...

Страница 15: ...0 2 4 39 558 896 2029 0 3 4 37 552 885 1999 0 3 4 60 576 929 1971 0 4 4 48 568 913 1947 0 4 4 68 588 957 1911 0 5 4 61 586 950 1897 0 5 4 79 608 989 1876 0 6 4 73 604 973 1857 0 6 4 87 620 1012 1821 0...

Страница 16: ...1666 0 60 1 2 2338 1 21 1992 0 92 1646 0 66 1 4 2359 1 32 2025 1 02 1648 0 72 1 6 2404 1 45 2056 1 13 1684 0 82 1 8 2088 1 24 1722 0 92 Standard Belt Drive Down Shot ESP W C Turns Open 0 1 2 3 4 5 CF...

Страница 17: ...2360 1 02 2119 0 81 1934 0 65 0 8 2470 1 30 2331 1 11 2111 0 89 1868 0 69 1 2296 1 18 2078 0 96 1840 0 75 1 2 2040 1 02 High Static Belt Drive Horizontal ESP In W C 0 Turns 1 Turn 2 Turns 3 Turns 4 Tu...

Страница 18: ...85 0 76 0 58 0 37 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 94 0 84 0 63 0 41 0 94 0 84 0 64 0 41 T 19 18 15 10 20 18 15 10 20 18 15 10 20 18 15 10 19 18 15 10 18 17 14 9 kW 2 46 2 50 2 58 2 65 2 63 2...

Страница 19: ...390 420 444 463 LO PR 105 112 122 130 111 118 129 137 115 123 134 143 121 129 141 150 127 135 147 157 131 140 152 162 85 1350 MBh 35 7 36 4 38 1 40 7 34 9 35 6 37 2 39 7 34 0 34 7 36 3 38 8 33 2 33 9...

Страница 20: ...78 0 59 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 96 0 86 0 65 0 42 0 96 0 86 0 65 0 42 T 19 18 15 10 20 18 15 10 20 18 15 10 20 18 15 10 20 18 15 10 18 17 14 10 kW 3 16 3 22 3 32 3 42 3 39 3 46...

Страница 21: ...3 423 455 480 501 LO PR 108 115 125 134 114 121 133 141 119 126 138 147 125 133 145 154 131 139 152 162 135 144 157 167 85 1800 MBh 47 0 47 9 50 1 53 5 45 9 46 7 49 0 52 2 44 8 45 6 47 8 51 0 43 7 44...

Страница 22: ...0 77 0 58 0 37 0 88 0 79 0 60 0 38 0 91 0 81 0 61 0 40 0 94 0 84 0 64 0 41 0 95 0 85 0 64 0 41 T 20 18 15 10 20 19 15 11 20 19 15 11 20 19 15 11 20 19 15 11 19 17 14 10 kW 4 01 4 09 4 22 4 35 4 31 4 4...

Страница 23: ...3 431 464 490 511 LO PR 105 112 122 130 111 118 129 137 115 123 134 143 121 129 141 150 127 135 147 157 131 140 152 162 85 2250 MBh 61 4 62 6 65 6 69 9 60 0 61 1 64 0 68 3 58 5 59 7 62 5 66 7 57 1 58...

Страница 24: ...0 80 0 72 0 54 0 35 0 82 0 74 0 56 0 36 0 85 0 76 0 58 0 37 0 88 0 79 0 60 0 38 0 89 0 80 0 60 0 39 T 21 19 16 11 21 19 16 11 21 19 16 11 21 19 16 11 21 19 16 11 19 18 15 10 kW 5 12 5 22 5 37 5 53 5 4...

Страница 25: ...118 129 137 115 123 134 143 121 129 141 150 127 135 147 157 131 140 152 162 85 2400 MBh 72 2 73 6 77 1 82 2 70 5 71 9 75 3 80 3 68 8 70 2 73 5 78 4 67 2 68 5 71 7 76 5 63 8 65 0 68 1 72 7 59 1 60 2 63...

Страница 26: ...arge return and supply openings Install with insulation facing up using the longer screws provided in the literature package RETURN SUPPLY 12 17 7 3 8 11 25 6 1 4 4 7 8 73 1 4 47 1 2 73 13 16 48 3 16...

Страница 27: ...coil electric heat and gas furnace Leave a clearance of 48 on all other sides of the unit for possible compressor removal or service access and to ensure proper ventilation and condenser airflow Do n...

Страница 28: ...ons are shown in Roof Curb Installation Instructions Manual Refer to the Roof Curb Installation Instructions for proper curb installation Curbing must be installed in compliance with the National Roof...

Страница 29: ...support before locating and mounting the curb and package unit Duct work must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit...

Страница 30: ...LE PLUG AND ATTACH FEMALE PLUG TO ECONOMIZER ACCESSORY 6 DIAGRAM SHOWS FACTORY SPEED TAP SETTINGS WH GR TB1 F LPS YL PK YL BL RD OR Y1 Y Y2 YL W Y Y2 BL G R OR W NO ECONOMIZER G OR YL RD Y Y2 Y1 PK WH...

Страница 31: ...COM TERMINAL ON EBTDR AND PLACE WIRE REVMOVED FROM COM ON EMPTY M1 OR M2 TERMINAL 3 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER 4 USE COPPER CONDU...

Страница 32: ...MR R EM FC GND HPS HVDR LPS LVDR LVJB PB PLF RVC RCCF TB1 TR 3 C 1 C C 24V PLF2 C T3 L3 BLOWER CONTACTOR CONTACTOR CONDENSER MOTOR CONDENSER MOTOR RELAY COMPRESSOR DEFROST CONTROL DEFROST THERMOSTAT E...

Страница 33: ...DS ARE ENERGIZED THE HIGHER SPEED SETTING IS USED 3 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER 4 USE COPPER CONDUCTORS ONLY USE N E C CLASS 2 WIRE...

Страница 34: ...G TO THE ECONOMIZER ACCESSORY 4 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER T2 O G P L F 1 THERMOSTAT 3 6 F 208 240 460 575 3 60 0140L00427 REV B Y...

Страница 35: ...FEMALE PLUG CONNECTOR RUN CAPACITOR FOR CONDENSER FAN TERMINAL BLOCK 24V SIGNAL TRANSFORMER TR OF OVER CURRENT PROTECTION SEE UNIT RATING PLATE FOR TYPE AND SIZE 208 240V 208 240 1 60 T2 2 1 N G 208...

Страница 36: ...HAILGD03 Condenser Coil Hail Guard 3 5 tons HAILGD04 Condenser Coil Hail Guard 6 tons Convenience Outlet Non Powered Convenience Outlet Powered DNECONGS3672B Downflow Economizer 3 6 tons DNSQRRND36B D...

Отзывы: