10 www.goodmanmfg.com
SS-CPC36-72
h
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, h
eat
m
ode
) — 6 t
ons
kW Correction Factor for 3-Phase Units
Supply Voltage
240
230
220
210
Correction Factor
1
0.92
0.84
0.77
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
Minimum Airflow for Electric Heat
Heater Size
Minimum CFM
10
2,100
15
2,100
20
2,100
25
2,100
Model and
Heat Kit Usage
MCA¹ @
208 / 240V
MOP² (amps)
@ 208 / 240V
Actual kW &
BTU @ 240V
Recommended
Airflow Range
CPC072XXX3BXXX
31
45
EHK3-10
36
45
10
2,100 - 2,700 CFM
EHK3-15
51
60
15
2,100 - 2,700 CFM
EHK3-20
66
70
20
2,100 - 2,700 CFM
EHK3-25
81
90
25
2,100 - 2,700 CFM
Model and
Heat Kit Usage
MCA¹
@ 480V
MOP² (amps)
@ 480V
Actual kW &
BTU @ 480V
Recommended
Airflow Range
CPC072XXX4BXXX
16
25
EHK4-10
18
25
10
2,100 - 2,700 CFM
EHK4-15
26
30
15
2,100 - 2,700 CFM
EHK4-20
33
35
20
2,100 - 2,700 CFM
EHK4-25
41
45
25
2,100 - 2,700 CFM
Model and
Heat Kit Usage
MCA¹
@ 575V
MOP² (amps)
@ 575V
Actual kW &
BTU @ 575V
Recommended
Airflow Range
CPC072XXX7BXXX
13
15
EHK7-10
15
20
10
2,100 - 2,700 CFM
EHK7-15
22
25
15
2,100 - 2,700 CFM
EHK7-20
28
30
20
2,100 - 2,700 CFM
EHK7-25
34
35
25
2,100 - 2,700 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection Device
Note:
All heaters have single-point entry kit