42
Cleaning & Maintenance
Model: FSH-2, FSH-2A-99
Hood design incorporates various interlock switches to ensure that the unit will shutdown if certain conditions exist which
are not consistent with safe and effective operation. The interlocks should be inspected and tested
MONTHLY
as described
below. Use the
Maintenance & Service Log
to record completion of testing. If problems are detected, contact
GILES
or an
authorized service provider.
1.
Door Interlock Test:
Start hood. With hood running, unlatch and slightly lift the bottom lip of the filter access
cover to confirm that hood powers
OFF
when cover is lifted and the fryer under the hood turns
OFF
, or cannot be
turned
ON
.b
2.
Baffle Filter Test:
Remove baffle filter then turn
ON
hood power. Verify that the red
[FILTER MISSING]
light
turns
ON
and the
[FRYER POWER]
light turns
OFF
. Check to ensure that fryer under hood will not turn
ON
.
Reinstall the baffle filter. See
Sections 4.02.2 & 4.02.3, Removal & Installation
.
3.
Charcoal (and HEPA) Filter Test:
Same procedure as
#2
except perform for the charcoal filter. Reinstall filter.
See
Sections 4.02.6, 4.02.7, Removal & Installation
. Same procedure applies for a
HEPA filter
, if equipped.
4.
E.A.C. Filter Test (N/A for HEPA Filter Version):
Same procedure as
#2 & #3
except remove the E.A.C. collector
cell, close and latch filter cover. Turn
ON
hood power. Verify that
[WASH]
light is
ON,
along with the amber
[FRYER POWER]
light. Wait approx. two (2) minutes. A beeping tone alarm should begin sounding. Shortly, the
[FRYER POWER]
light should turn
OFF.
Check to ensure that fryer under Hood will not turn
ON
. Reinstall the
E.A.C. cell. See
Section 4.02.4. & 4.02.5, Removal & Installation
.
5.
Filter Clogged Test:
Perform this test ONLY after installing new Charcoal Filter
.
Start hood normally and allow
to run. Use cardboard or other material to completely block Hood exhaust outlet, holding it firmly in place so that
no air is escaping
.
Within a few seconds, a continuous tone alarm should begin sounding and the
[FRYER POWER]
light should turn
OFF.
Check to ensure that fryer under Hood will not turn
ON
. Remove the obstruction; the
alarm should silence and the
[FRYER POWER]
light should turn
ON
again.
Should any of these tests fail to yield the described results, contact a factory-authorized service company and have the
unit evaluated and repaired. Any
Giles Manufacturer’s Representative
can provide information about nearby authorized
service providers, or call
GILES Services
at 800-554-4537
for assistance in locating a Representative or service provider.
5.03.1
Monthly Hood Interlock Inspection (Can Generally be Performed by User)
The self-contained fire extinguishing system in the hood must be maintained in accordance with the
Standard for Wet
Chemical Extinguishing Systems, NFPA 17A
and with the instructions of the system installer.
All inspection, maintenance, troubleshooting, repairs and general servicing of the fire extinguishing system must be
performed by an authorized
Ansul® Distributor/Dealer
. Required maintenance activities are described in the subsequent
sections.
5.04
Fire Suppression System Maintenance
Continued on Next Page
Содержание FSH-2
Страница 2: ......
Страница 4: ......
Страница 28: ...18 Installation Model FSH 2 FSH 2A 99 ...
Страница 36: ...26 Overview Model FSH 2 FSH 2A 99 ...
Страница 45: ...35 Operation Model FSH 2 FSH 2A 99 NOTES ...
Страница 46: ...36 Operation Model FSH 2 FSH 2A 99 ...
Страница 58: ...48 Parts List Model FSH 2 FSH 2A 99 1 2 3 5 6 8 7 4 Not shown 7 02 Ventless Hood Front ...
Страница 64: ...54 Parts List Model FSH 2 FSH 2A 99 Notes ...
Страница 65: ......