10
Installation
Model: FSH-2, FSH-2A-99
Safety interlocks will disable power supplied to the appliance under the hood if any of the following conditions
occur:
• Filter becomes excessively dirty or air flow through hood is obstructed.
• Filter is missing or not installed correctly.
• The fire extinguishing system has been activated, or is not armed.
• Filter access cover is removed or not installed correctly (hood blower will also shutdown).
Model FSH-2:
1. The
Model FSH-2 Hood
requires a separate, field installed, interlocking circuit with an appropriately sized
contactor, connected as shown by this diagram.
Customer supplied.
2. Remove Cover from Interlock Tie-
In Box and run appropriately sized
conduit and wire to a hood
&
appliance connection box
(supplied by customer)
. Allow
enough conduit and wire so the
hood can be accessed for cleaning
and servicing.
3. Make appropriate connections.
See diagram.
4. Reinstall Interlock Tie-In Box
Cover.
Model FSH-2A-99:
1. The appliance interlock contactor feature is built-in on this model Hood. Refer to
Figure 2.03.1 (B)
and the
wiring diagram supplied with the unit for field wiring information.
2.03.3 Hood & Appliance Interlock Connection
Содержание FSH-2
Страница 2: ......
Страница 4: ......
Страница 28: ...18 Installation Model FSH 2 FSH 2A 99 ...
Страница 36: ...26 Overview Model FSH 2 FSH 2A 99 ...
Страница 45: ...35 Operation Model FSH 2 FSH 2A 99 NOTES ...
Страница 46: ...36 Operation Model FSH 2 FSH 2A 99 ...
Страница 58: ...48 Parts List Model FSH 2 FSH 2A 99 1 2 3 5 6 8 7 4 Not shown 7 02 Ventless Hood Front ...
Страница 64: ...54 Parts List Model FSH 2 FSH 2A 99 Notes ...
Страница 65: ......