14
Installation
Model: FSH-2, FSH-2A-99
The fire suppression system used in the
Giles Ventless Hood
is the
ANSUL® R-102 Restaurant Fire Suppression
System (Standard UL 710B Listed)
.
Final field set-up, charging, certification and arming of the system must be
performed by an authorized Ansul distributor in accordance with the system listing.
The fire suppression system is designed and UL-listed to provide fire protection for cooking appliances such as
fryers. It a mechanical system that automatically protects 24 hours per day. The factory-installed system includes
piping, nozzles (appliance & plenum), Automan release mechanism, detector link brackets, conduit for link cabling,
exhaust outlet fire damper and a 1-1/2 gal. stainless steel tank
.
Field set-up by an Ansul agent includes, but may not be limited to, installation of proper fusible detector links and
cabling, filling provided tank with wet chemical suppressant and installing, installation of remote manual activation
station, installing a compressed gas discharge cartridge, testing, certifying and arming the system.
Parts and labor
necessary for system field set-up is the responsibility of the customer and is not included with hood purchase
.
Appliance Link:
If less than 3” [76.2] to edge of cooking surface
use 165
°
F link
supplied & installed by ANSUL
If more than or equal to 3” [76.2] to edge of
cooking surface use 135
°
F link
supplied & installed by ANSUL
Plenum Link 165
°
F
supplied & installed by ANSUL
Damper Link 285
°
F
factory-installed
LT-20 R Cartridge
supplied & installed by Ansul
Appliance cooking surface
INCHES [mm]
2.05
Fire Suppression System
2.05.1 Detector Links & Gas Cartridge Location
Содержание FSH-2
Страница 2: ......
Страница 4: ......
Страница 28: ...18 Installation Model FSH 2 FSH 2A 99 ...
Страница 36: ...26 Overview Model FSH 2 FSH 2A 99 ...
Страница 45: ...35 Operation Model FSH 2 FSH 2A 99 NOTES ...
Страница 46: ...36 Operation Model FSH 2 FSH 2A 99 ...
Страница 58: ...48 Parts List Model FSH 2 FSH 2A 99 1 2 3 5 6 8 7 4 Not shown 7 02 Ventless Hood Front ...
Страница 64: ...54 Parts List Model FSH 2 FSH 2A 99 Notes ...
Страница 65: ......