10. MAINTENANCE/INSPECTION CHECKLIST
MAINTENANCE/INSPECTION CHECKLIST
(NOTE:
Maintenance/inspection items are monthly unless otherwise specified.
)
Evaporator Model No.:
Evaporator Serial No.:
Technician:
Date:
Temperature/Humidity set at:
°F % RH
Air Filters:
☐
Inspect and replace (if required)
☐
Inspect grille area and ensure unrestricted
Air Distribution Section
☐
Check restriction of grilles and discharge
louvers
Electrical Section
☐
Inspect fuses
☐
Inspect/tighten all wire connections
☐
Inspect contactor operation
☐
Check operation sequence
☐
Check calibration of change over
thermostat (Energy Saver system only)
Controls
☐
Check unit control operation
☐
Check operation of the following:
☐
High water alarm
☐
Pressure differential switch
☐
Fan current sensing switch
EC Plug Fan Section:
☐
Check plug fan wheel movement to be free and clear of any debris
Record motor voltage Record motor amp draw
Fan#1 L1 V L2 V L3 V L1 A L2 A L3 A
Fan#2 L1 V L2 V L3 V L1 A L2 A L3 A
Fan#3 L1 V L2 V L3 V L1 A L2 A L3 A
Record fan wheel speed (RPM) Fan#1 RPM Fan#2 RPM Fan#3 RPM
Humidifier (Steam Generator) is equipped:
☐
Inspect drain valve/trap/drain line
☐
Check for leaks (make-up water/hoses)
☐
Check humidifier canister (replace if needed)
☐
Check and clean fill strainer
☐
Check operation
Record humidifier amp draw
L1
A L2
A L3
A
Reheat
Refrigeration Piping