41
For testing and during start-up each gForce unit is provided with manual override slide switches.
There are seven (7) slide switches. One for each of the following functions:
Figure 12 Manual Override Switch Board
All automatic control is disabled but the safety switches remain functional. Simply slide the
manual switches to energize the fan, compressor(s), humidification, reheat and other functions
(as applicable).
The fan speed of the Electronically Commutated (EC) plug fan motor can be adjusted from 0 to
10 volts DC by adjusting the potentiometer at the left of the Fan Speed switch. The fan speed
will increase 10% of the fan base speed for each one (1) volt adjustment (e.g., one (1) volt equals
10% speed). At ten (10) volts the motor is at full speed.
WARNING:
Do not leave the unit in manual override. Slide the switches
to the OFF position when completing testing and/or start-up. An alarm will
be activated if units are left in the ON position.
3.17. Plug Fan Current Sensing Switch
Unit with backward curve plenum fans with electronically commutated (EC) motor (plug fan) use
a current sensing relay (CT) as a safety to alarm when the air flow is unusually low or no air flow.
See section
9.17 Current Sensing Switch Adjustment (Plug Fans Only)
regarding switch adjustment.
3.18. Wiring Diagrams
Every Data Aire evaporator, condenser, condensing unit or fluid cooler comes with a wiring
diagram. These diagrams are ladder type schematics intended for service personnel. The intent
is to allow the technician to understand the wiring details associated with the electrical
components and how they interface with the controls as well as peripheral equipment (including
secondary heat exchangers).