23
Hot Gas Lines (Dual Circuit Systems)
Unit kW
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
Horizontal
& Vertical
Down
Vertical
Up
Horizontal
& Vertical
Down
Vertical
Up
Horizontal
& Vertical
Down
Vertical
Up
Horizontal
& Vertical
Down
Vertical
Up
70
7/8”
7/8”
1-
1/8”
7/8
”
1-
1/8”
7/8”
1-
1/8”
7/8”
91
1-
1/8”
1-
1/8”
1-
1/8”
1-
1/8”
1-
3/8”
1-
1/8”
1-
3/8”
1-
1/8”
125
1-
1/8”
1-
1/8”
1-
3/8”
1-
1/8”
1-
3/8”
1-
1/8”
1-
3/8”
1-
1/8”
Liquid Lines (Dual Circuit Systems)
Unit kW
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
70
7
/8”
7
/8”
7
/8”
7
/8”
91
7/8”
7/8”
7/8”
7/8”
125
1-1/8
”
1-1/8
”
1-1/8
”
1-1/8
”
NOTE:
1. If equivalent piping length falls between two columns above,
choose the longer equivalent length.
2. Dual circuit units should use the same line size on both circuits.
3. If hot gas line refrigerant flow is upward, use
“Vertical Up”.
4. If hot gas line refrigerant flow is downward, use
“Horizontal & Vertical
Down
”.
2.15. Connection Sizes, Air Cooled Units
Model Number
Liquid Line
Hot Gas Line
GUA* 022
5/8” (16 mm) O.D.
5/8” (16 mm) O.D.
GUA* 036
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 045
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 070
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 091
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 125
1-
1/8” (29 mm) O.D.
7/8” (22 mm) O.D.
NOTE:
Field connections at the indoor evaporator and remote
condenser will not necessarily be the same as the field pipe size
required.