72
side panels must remain closed when determining if an adjustment is necessary.
In general on Data Aire gForce floor units, the filters are removable from the front of the unit
unless otherwise specified.
NOTE:
Replace the air filters with same filter size and type. Any new
filters manufacturer must be U.L. and CSA approved (Classified).
9.5.1. Downflow Unit Filter Replacement Procedure
•
Turn OFF the disconnect switch to all remote electric facility power to the unit with the
external disconnect.
•
If a return duct is not installed, use an OSHA approved stepladder or ladder, to remove
filters from the top of the unit. If a return air duct is installed, the filters can be removed by
opening the access door(s) and lifting the filters out through the doors.
•
Replace with new filters of equal size and type.
•
Install the filters in with the proper direction of the airflow.
•
Test the operation of the filter differential pressure switch. The unit door(s) must be in place
and closed for proper differential pressure setpoint.
•
Turn ON the electrical facility power to the unit. After the controller completes the self-
checks, the fan or blowers will start.
•
Temporarily cover approximately 75% of the return air opening using heavy cardboard or
similar material to adjust the filter differential switch.
•
Adjust the switch setpoint, if necessary.
9.5.2. Upflow Unit Filter Replacement Procedure
•
Turn OFF the disconnect switch to all remote electric facility power to the unit with the
external disconnect.
•
Open the front access door(s) and remove the filters by lifting them up and maneuvering
the filter downward and out of the unit.
•
Replace with new filters of equal size and type.
•
Install the filters in the proper direction of the airflow.
•
Test the operation of the filter differential pressure switch. The unit door(s) must be in place
and closed for proper differential pressure setpoint.
•
Turn ON the electrical facility power to the unit. After the controller completes the self-
checks, the fan or blowers will start.
•
Temporarily cover approximately 75% of the return air opening using heavy cardboard or
similar material to adjust the filter differential switch.
•
Adjust the switch setpoint, if necessary.