When done, press the Auto on key to return to normal operation controlled by the dap4
controller.
NOTE:
If more information is required, see the full operating manual for
the Danfoss VFD drive system.
7.6.
High Pressure Cutout Switch
Each refrigerant circuit is protected by a high-pressure cutout switch with manual reset
button. The switch is typically located in the evaporator near the compressor. The high-pressure
switch rating is:
R-410A Refrigerant
Setting
Cut-out (Open)
575 PSI (3965 kPa)
Cut-in (Close)
Manual Reset
7.7.
Low Pressure Cutout Switch
Each refrigerant circuit has a low-pressure cutout switch which features SPST open-low switch
action and automatic reset. The switch is typically located in the evaporator near the
compressor. The low-pressure switch rating is:
R-410A Refrigerant
Setting
Cut-out (Open)
50 PSI (345 kPa)
Cut-in (Close)
90 PSI (621 kPa)
7.8.
Liquid Line Solenoid Valve
Liquid line solenoid valve(s) (LLVS) are a standard feature on this unit. The LLSV are direct
acting, NC (normally closed; i.e. closed when de-energized) solenoid operated valve(s). This
has the advantage that the valve is closed when the system is not running and when the solenoid