UFO-NT
36
WC control
15 WC control
Only operates with fail-safe electric strike. For connection and configuration, see chapter 13 "Electric strike".
KA
23
KA
2
24V
PE1, PE2
51
PE1
2
24V
52
PE2
+
+-
GND
1
2
24V
55
56
GN
1
PA1 PA2
57
PA1A
PA1B
PA2
oder
-
+
-
+
K
23
KA
2
24V
PE1, PE2
51
PE1
2
24V
52
PE2
+-
GND
1
2
24V
55
56
GN
1
PA1 PA2
57
PA1A
PA1B
PA2
oder
-
+
-
+
1
GND
1
2
2
3
1
2
4
4
2
3
oder
1
Internal push button (switch unit with illuminated display)
2
Illuminated OCCUPIED display
3
External push button (switch unit with illuminated display)
4
Signal horn SLH220 (optional)
Function
The control recognises the operating function "WC control" based on the parameter set for the configurable
input (PE1, PE2). If the WC is not occupied, the door is in automatic mode and is in the closed position. The OC-
CUPIED signs are off.
When the "external push button" is activated, the WC door is opened. Once someone has entered the cubicle,
the WC door is switched to exit only mode by pressing the "Internal push button" and the external push button is
blocked. The OCCUPIED signs light up. The WC door is locked by the fail-safe electric strike
*)
. Pressing the "Inter-
nal push button" again switches the mode of operation back to automatic. The OCCUPIED signs go out. The door
opens and the "External push button" is cleared again. If the closed and locked door is opened manually from
the inside or if a contact sensor mechanical contact KB is triggered, the mode of operation also switches back to
automatic. The door can then be restarted by pressing KA
When the WC is monitored for permanent locking, the "WC alarm" signal is triggered after 30 minutes and an
acoustic signal (signal horn) is switched on. The time cannot be set.
The operating function “WC control” is cancelled in the following cases:
à
When the door is closed and locked and manual passing has been detected.
à
When the door is opened from the outside using the mechanical contact (KB) (e.g. in case of an emergency).
In both cases the door can then be activated via the “Outside push button”.
In the event of a power failure, the fail-safe electric strike is released and the door can be opened manually.
*)
Locking with a panic motor lock is also possible (optional)
Illuminated OCCUPIED display
The illuminated OCCUPIED display (PA1 or PA2) is activated when switching to the exit only mode of operation.
Parameter setting:
à
DPS:
à
Set
e1
or
e2
to
21
(WC control), depending on the input used.
à
Set
a1
or
a2
to
1 4
(illuminated display OCCUPIED).
à
Set
a1
or
a2
to
2 4
(WC control alarm)
.
à
Set
O ®
to
the desired time (0–60 s).