Setting the alarm threshold temperature
Use the
or
button key to set the maximum floor-level
temperature above which the thermostat suspends heating
to prevent any possible damage (the value is expressed as
tenths of °C, and can be set from 150 to 1000 in steps of
100). This parameter is only visible if the NTC temperature
sensor connected to the thermostat has been enabled as a
temperature probe (TEMP).
To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
Setting the local relay
Use the
or
button key to set the operating mode of the
relay on the thermostat (OFF = disabled, HEAT =
management of heating valve, COOL = management of
cooling valve, BOTH = management of cooling
valves).
To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
Enabling the supplementary parameter pages
Use the
or
button key to enable/disable the three sets
of functions that the device configuration parameters are
divided into (G = General parameters, GF = General +
Operating parameters, GFC = General + Operating +
Control parameters). To confirm your choice and move on
to the next parameter, press the
button key within 30
seconds.
If the local modification function has been enabled from the “Enabling the supplementary
parameter pages” menu for the General Parameters group only (option G), press the
button key to return to the start of the parameter configuration menu. Otherwise, continue
with the configuration of the next group of parameters.