PWM PROPORTIONAL-INTEGRAL

The PWM control algorithm, used to control the temperature adjustment system, allows
you to drastically reduce the times subject to thermal inertia and introduced by the two-
point control. This type of control involves the modulation of the impulse duty-cycle,
represented by the temperature adjustment system activation time, on the basis of the
difference between the fixed setpoint and the temperature effectively detected. Two
components are needed to calculate the output function: the proportional component
and  the  integral  component,  used  to  improve  the  response  in  order  to  reach  the
temperature at the fixed setpoint. Once the proportional band has been defined (from
setpoint to setpoint - 

for heating mode, from setpoint to se 

for cooling

mode), its width determines the extent of the system response: if it is too narrow, the
system will be more reactive but with swings; if it is too wide, the system will be slower.
The ideal situation is one where the band is as narrow as possible, without swings. The
integration time is the parameter that determines the action of the integral component.
The longer the integration time, the slower the modification of the output and hence the
slower the system response. If the time is too short, the threshold value will be exceeded,
and the function will swing around the setpoint.

cycle time

cycle time

set-point

set-point

A

IR

-

CONDITIONING

H

EATING

set-point

set-point

Содержание Chorus GW 10 765H

Страница 1: ...ONE PROGRAMMING MANUAL MANUEL DE PROGRAMMATION MANUAL DE PROGRAMACI N PROGRAMMIERHANDBUCH Termostato T H Easy da incasso Easy T H thermostat flush mounting Thermostat T H Easy encastrer Termostato T H...

Страница 2: ......

Страница 3: ...ly 4 Position of the commands 5 Description of the commands 6 Control modes 7 Operating mode 7 Thermostat operation statuses 9 USER INSTRUCTIONS Normal operation 10 Setting the parameters 12 Easy chan...

Страница 4: ...ructions for correct assembly are contained in the installation manual supplied with the product and which can also be downloaded from the website www gewiss com More information about the programming...

Страница 5: ...buttons that can always be accessed 9 10 8 7 2 1 3 4 6 18 5 16 17 11 15 12 14 13 19 Position of the commands ATTENTION If the display backlighting is enabled only the screen will light up when any one...

Страница 6: ...flash the speed set manually or by algorithm is waiting to be activated Thermostat in Slave operation Temperature measured Temperature relative humidity specific humidity dew point temperature measur...

Страница 7: ...dependent on any other device In the autonomous control mode you can alter the setpoint as you wish and enable the thermostat to receive remote mode setting commands OFF Economy Pre comfort Comfort an...

Страница 8: ...e adjustment system is switched OFF In this case the thermostat uses the fixed high temperature protection setpoint only reactivating the cooling system if the room temperature exceeds TPROTEZIONE ALT...

Страница 9: ...n to flash Subsequently the thermostat sends the activation command every 60 seconds until it receives confirmation Operation with active fan coil control If the fan coil control function has been act...

Страница 10: ...displayed To confirm a page press the button key or wait for the 30 second time out period to elapse Pages relating to the thermostat control type HVAC Choosing the HVAC mode pre comfort comfort econ...

Страница 11: ...tch off If the displayed page relates to the thermostat and the control type has been set in setpoint press the button key to switch off the device manually Press the button key again to reactivate th...

Страница 12: ...hen the button key is pressed To return to the screen listing the pages that can be viewed keep the button key pressed Use the or button key to scroll through the sequence To confirm a page press the...

Страница 13: ...age relates to the humidity section the Set menu concerning the selected humidity threshold will be shown The parameters relating to the thermostat and humidity are collected into three functional gro...

Страница 14: ...eter press the button key within 30 seconds NB if red blue is chosen the thermostat background will be white during the idle phase heating and cooling valves deactivated of normal operation turning re...

Страница 15: ...e 10 or leave unaltered 0 the light intensity value detected by the built in light sensitive sensor To confirm your choice and move on to the next parameter press the button key within 30 seconds Exte...

Страница 16: ...agement of cooling valve BOTH management of heating cooling valves To confirm your choice and move on to the next parameter press the button key within 30 seconds Enabling the supplementary parameter...

Страница 17: ...ction and continue with the next parameter press the button key within 30 seconds Use the button keys or to set the weight of the blue component BLU in the backlighting of the display value can be set...

Страница 18: ...ing Adjust the value of TPRE COMFORT with the aid of the button keys To confirm the set value press the button key within 30 seconds Setpoint setting When the symbol appears the temperature value begi...

Страница 19: ...he set value press the button key within 30 seconds Setpoint setting When the symbol appears the temperature value begins flashing Adjust the value of Teconomy with the aid of the button keys To confi...

Страница 20: ...e adjustment system 2 common logic 4 separate logic The common control logic is associated with 2 way systems with one single valve for heating and cooling The separate control logic is associated wit...

Страница 21: ...e activates the cooling system by sending the relative command to the actuator that manages it when the measured temperature reaches the fixed setpoint value the device deactivates the cooling system...

Страница 22: ...ach the temperature at the fixed setpoint Once the proportional band has been defined from setpoint to setpoint for heating mode from setpoint to setpoint for cooling mode its width determines the ext...

Страница 23: ...rature has been reached it continues to provide a limited contribution to compensate for the environmental heat dispersion Setting the proportional band Use the button keys to set the value of the pro...

Страница 24: ...objects to manage the individual speeds The figures below refer to the control of the speeds of a fan coil with three operating stages for heating and cooling The charts show that each stage has a hy...

Страница 25: ...ivated when the temperature value is lower than the setpoint valve 1heat 2heat 3heat value in heating mode or higher than the setpoint valve 1cond 2cond 3cond value in cooling mode and deactivated whe...

Страница 26: ...ntial for speed 2 Use the or button key to set the value of the adjustment differential of fan coil speed 2 the gap can be set from 0 1 C to 2 0 C To confirm your choice and move on to the next parame...

Страница 27: ...emote device e g the GSM Easy remote control During normal thermostat operation when a remote command is received the symbol will flash as long as the active mode is the one set via the remote device...

Страница 28: ...REC pre comfort COMF comfort or OFF This screen is only visible if the remote element control type has been set in HVAC mode via the Easy configurator To confirm your choice and move on to the next pa...

Страница 29: ...button keys SLA Slave Used to set from remote with other Easy devices the type heating cooling and HVAC operating mode or Setpoint of the thermostat Examples of devices that can be used Easy timed the...

Страница 30: ...ed 2 of the heating fan coil HS3 Speed 3 of heating fan coil Used to send the ON OFF command to the channel of the Easy actuator that controls speed 3 of the heating fan coil CS1 Speed 1 of cooling fa...

Страница 31: ...e 2 Easy temperature adjustment probe SE3 Temperature adjustment probe 3 Used to control remote device 3 Easy temperature adjustment probe SE4 Temperature adjustment probe 4 Used to control remote dev...

Страница 32: ...CTION 24 C 26 C 28 C 35 C Temperature measurement unit C Control logic common 2 ON OFF points Adjustment differential control with 2 points 0 2 C Control modes Autonomous Back lighting colour White Ic...

Страница 33: ...phases with the backlighting enabled there may be slight alterations in the local temperature so the device prevents the updating of the measurement for a few minutes in order to guarantee the accura...

Страница 34: ...hermostat has no buffer battery so the time setting is lost if there is a BUS voltage failure The time can only be reset manually Is it possible to understand whether the potential free contact input...

Страница 35: ...35...

Страница 36: ...2 della Direttiva Europea 2004 108 CE si informa che responsabile dell immissione del prodotto sul mercato Comunitario According to article 9 paragraph 2 of the European Directive 2004 108 EC the resp...

Отзывы: