USER INSTRUCTIONS
E
N
G
L
I
S
H
15
Back-lighting timing
Use the
or
button key to set the minimum duration of
the inactivity time of the user before the back-lighting is
automatically deactivated (the gap can be set from 10 to
180 seconds). This parameter is only visible if the back-
lighting is active. To confirm your choice and move on to
the next parameter, press the
button key within 30
seconds.
Back-lighting intensity
Use the
or
button key to choose how to manage the
back-lighting intensity (MAN = fixed value; SENS = light
sensitive sensor). This parameter is only visible if the back-
lighting is active. If the type of management is MAN, use
the
or
button key to choose the required percentage
of light intensity (the gap can be set from 30 to 100%).
If the type of management is SENS, use the
or
button
key to increase (+10%), decrease (-10%) or leave unaltered
(0%) the light intensity value detected by the built-in light-
sensitive sensor.
To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
External temperature sensor
Use the
or
button key to set the function of the NTC
temperature sensor connected to the thermostat (OFF =
disabled; TEMP = enabled as temperature probe; FLO =
enabled as underfloor probe). To confirm your choice and
move on to the next parameter, press the
button key
within 30 seconds.
Impact of the external temperature sensor on the
measured temperature calculation
Use the
or
button key to set the weight (%) of the
external temperature sensor in the calculation of the
temperature measured by the thermostat (the value can be
set from 10% to 100%, in steps of 10). This parameter is
only visible if the NTC temperature sensor connected to the
thermostat has been enabled as a temperature probe on
the previous screen. To confirm your choice and move on
to the next parameter, press the
button key within 30
seconds.