System malfunctions
Checking installation and function
When you have remedied system malfunctions, perform a function test as follows.
■
■
Check the alarm functions by exceeding both the upper and lower limit values for MIN alarm and MAX
alarm set in the level controller NRR 2-60 / NRR 2-61. In this case, the equipment must behave as if
there were an alarm.
■
■
Check the switchpoints when bringing into service and every time the NRG 26-60 level electrode
is replaced.
The system faults in the NRG 26-60 level electrode lead to a fault shutoff in the level controller
NRR 2-60 / NRR 2-61. The alarm contacts switch without delay. For information on
precisely how the alarm contacts function, please read the Installation & Operating Manual of
the corresponding NRR 2-60 or NRR 2-61.
If you require assistance, please tell us the indicated fault code.
In the event of malfunctions or faults that cannot be remedied with the aid of this Installation &
Operating Manual, please contact our service centre or authorised agent in your country.