NRG 26-60 - Installation & Operating Manual -
819875-00
Bringing into service
Key to parameters:
■
■
099.9 = actual value display, the currently measured value, based on the calibration 0 - 100 %
■
■
GrP
= controller group (effect on URB 60 / SPECTOR
control)
■
■
bd.rt = baud rate
■
■
°C.in = display ambient temperature of housing
■
■
CAL.L = lower bound calibration to 0 %
■
■
CAL.P = measurement range calibration to an intermediate value above 25 % (alternative to CAL.H)
■
■
CAL.H = upper bound calibration to 100 %
■
■
Filt
= filter constant
■
■
diSP = display test trigger
■
■
ConP = activation of compatibility mode; for operation with SPECTORconnect, do not
change setting (ConP = oFF)
Notes on changing the communication parameter “GrP or bd.rt”
In general, all GESTRA AG CAN bus devices are delivered ex-works with pre-set communi-
cation parameters that make it possible to bring a standard system into service without any
changes.
Observe the following rules if you have to make changes to the communication
parameters:
■
■
Set the same baud rate for all bus participants.
■
■
Perform the following functions on the URB 60 visual display and operating unit or on the
SPECTOR
control, in order to apply the changed communication parameters:
■
◆
Device list - Reimport
Observe the information in the operating manual of the
URB 60 visual display and operating unit or SPECTOR
control.