Allocation of the display and LEDs to the respective operating state of the level electrode:
Start
Switch on
supply voltage
All LEDs light up - test
Display:
S-xx = software version
t-03 = equipment type NRG
26-60
The system is started and tested.
The LEDs and display are tested.
Normal operation
The level electrode
is immersed within the set
measurement range
Display:
e.g. 047.3
LED 2
:
Operating LED lights up green
Display of the current level as a % of the calibrated
measurement range.
See the following pages for more information and tables.
Behaviour in the event of a malfunction (fault code display)
On the occurrence of a fault
Display:
e.g. E005
LED 1
:
Alarm LED lights up red
A fault code is permanently displayed,
fault codes see page 44
A malfunction is active
LED 2:
Operating LED is OFF
A fault is present
■
■
The malfunction or faulty state is transferred to the level controller NRR 2-60 / NRR 2-61 via CAN data telegram.
■
■
Here, the malfunction triggers an immediate alarm.
Malfunctions in the electrode cannot be acknowledged.
When the malfunction is cancelled, the message in the display also disappears. The NRR 2-60
/ NRR 2-61 level controller returns to normal operation.
Faulty equipment jeopardises system safety.
■
■
If the level electrode does not behave as described above, it may be faulty.
■
■
Perform failure analysis.
■
■
The NRG 26-60 level electrode may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace faulty equipment with identical equipment from GESTRA AG.
Starting, operation and testing