NRG 26-60 - Installation & Operating Manual -
819875-00
System malfunctions
The display or control reacts too slowly or too quickly to changes in the fill level.
Possible causes if no error messages appear
Remedy
The damping coefficient “FiLt” setting
is invalid.
Correct the damping coefficient “FiLt”.
The device fails to work. Display and LEDs do not illuminate.
Possible causes if no error messages appear
Remedy
Supply voltage failure.
■
■
Switch on the supply voltage.
■
■
Check all electrical connections.
The device fails to work. Display and LEDs illuminate.
Possible causes if no error messages appear
Remedy
The earth connection to the vessel is interrupted.
■
■
Clean the sealing surfaces and
■
■
screw in the level electrode with a metal sealing ring,
see page 23.
Flashing values from t-71 to t-75 appear in the display
Possible causes
Remedy
The ambient temperature of the electrode terminal box
is high, between 71 °C and 75 °C.
If the temperature rises above 75 °C, the fault code
E.027 (Overtemp Err) appears and a fault or alarm
shutoff occurs at NRR 2-60, NRR 2-61.
■
■
The ambient temperature around the terminal box must
be reduced, for example through cooling.