37
NRG 26-60 - Installation & Operating Manual -
819875-00
Bringing into service
Changing the controller group “GrP”
For setting the controller group, please also pay attention to the information in the Installation
& Operating Manual of the NRR 2-60 or NRR 2-61 level controller.
Note the setting instructions on page 35 and proceed as follows:
1.
Select the parameter “
GrP
”.
2.
Press and hold the rotary knob until the current controller group ID flashes on the display.
3.
Set the desired controller group (1 to 4). The controller groups correspond to the following
CAN bus node IDs:
Controller group 1 = node-ID 40
Controller group 2 = node-ID 45
Controller group 3 = node-ID 60
Controller group 4 = node-ID 65
4.
Save your set value by pressing the rotary knob for approx. 1 second.
Changing the baud rate “bd.rt”
You must set the same baud rate for all bus participants.
Note the setting instructions on page 35 and proceed as follows:
1.
Select the parameter “
bd.rt
”.
2.
Press and hold the rotary knob until the current baud rate flashes on the display.
3.
Set the desired baud rate (50 kBit/s or 250 kBit/s).
4.
Save your set value by pressing the rotary knob for approx. 1 second.