45
NRG 26-60 - Installation & Operating Manual -
819875-00
Fault code display
Fault code
Internal
designation
Possible faults
Remedy
E.012
FreqErr
Measurement signal frequency
Replace the level electrode
E.014
ADSReadErr
16-bit AD converter does not
respond
Replace the level electrode
E.015
UnCalibErr
Factory calibration invalid
(not measurement range
calibration)
Replace the level electrode
E.016
PlausErr
Plausibility error
in measurement range
Check the calibration of the
measurement range, repeat if necessary
E.019
V6Err
System voltage 6 V outside limits Replace the level electrode
E.020
V5Err
System voltage 5 V outside limits Replace the level electrode
E.021
V3Err
System voltage 3 V outside limits Replace the level electrode
E.022
V1Err
System voltage 1 V outside limits Replace the level electrode
E.023
V12Err
System voltage 12 V outside
limits
Replace the level electrode
E.024
CANErr
Communication failure
Check the baud rate, wiring and terminating
resistors
E.025
ESMG1Err
µC error
Replace the level electrode
E.026
BISTErr
µC periphery self-test error
Replace the level electrode
E.027
OvertempErr
PCB temperature,
ambient temperature > 75 °C
Check installation location. Lower the ambi-
ent temperature of the terminal box
(cool if necessary)
All E.013, E.017 and E.018 fault codes not listed here are available as reserves
Virtually all of the aforementioned fault codes can be caused by EMC interference. This is less
likely to be the case in the event of permanent faults, but should be considered for sporadic
fault messages.