NRG 26-60 - Installation & Operating Manual -
819875-00
Bringing into service
Activating URB 2 compatibility “ConP”
For operation with SPECTORconnect, do not
change setting (ConP = oFF).
1.
Select the parameter “
ConP
”.
2.
Press and hold the rotary knob until the current status flashes on the display.
3.
Set the required status (off / on).
ConP
=
on
:
This enables the display of the higher-resolution NRG 26-60 measured values on the
URB 2 operating terminal (by converting from 16 bit to 10 bit).
ConP = oFF:
16-bit resolution of the NRG 26-60 measured values.
4.
Save your set value by pressing the rotary knob for approx. 1 second.
Check the MIN and MAX limit values of the NRR 2-6x level controller by raising or lowering the
level
Incorrectly installed or bent level electrodes result in a loss of function that can jeopard-
ise system safety.
Proceed as follows every time you bring the NRG 26-60 level electrode into service or
change it:
■
■
Check the MIN and MAX limit values of the NRR 2-6x level controller by exceeding the upper
or lower level at the system’s operating point.
■
■
Never start up any system without first checking that switchpoints are correct.
■
■
The NRG 26-60 level electrode may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace a faulty device with an identical device from GESTRA AG.