Bringing into service
Select and set a parameter:
1.
+
-
Using the screwdriver, turn the rotary knob clockwise or anti-clockwise
until the desired parameter appears on the display, the set value
appears after approx. 3 seconds.
The display alternately shows the selected parameter with its current
value, e.g. bd.rt
“value”
bd.rt.
Turning the rotary knob to the right shows the following parameters in
sequence:
“Actual value”
GrP
bd.rt
°C.in
CAL.L
CAL.P
CAL.H
Filt
diSP
ConP
“Actual value”
Key to parameters, see page 36.
If you do not set a parameter within 10 seconds, the process is aborted (“quit”) and
the old parameter value is retained.
4.
+
-
Save your set value by pressing the rotary knob for approx. 1 second.
The response “donE” appears and the display returns to the parameters.
If you do not enter anything for 30 seconds, the display automatically shows the
actual value.
2.
+
-
Once you have selected a parameter, press the rotary knob and hold until the current
value of this parameter flashes on the display.
3.
+
-
Set the desired value.
Reducing/increasing the value
Each parameter has an individual, admissible value range.
By pressing the knob briefly, you can jump to the next digit. This is a more convenient