5.9
www.geniecompany.com
04-14
Figure 11
Figure 11 shows an example of a typical sensing edge installation. Left hand side is shown but
right hand is a mirror image of this.
1A) If the wiring from the sensing edge enclosure to the operator is a coiled cord or 2 wire
jacketed cord:
•
Install junction box 12” above the center of the door opening on same side as
sensing edge enclosure.
•
Secure one end of cord to junction box using a cable clamp.
1B) If connection is to be made through a take up reel cord:
•
Install on same side as sensing edge enclosure and above door opening and
slightly to the side.
•
Install junction box adjacent to take up reel and route the stationary cord from
the reel to the box and secure with a cable clamp.
2) Secure other end of cord (straight, coiled or reel) to sensing edge
enclosure using a cable clamp.
3) Connect wires of cord to sensing edge using wire nuts or other suitable wire connectors.
4) Run a straight 2 wire cord from the junction box (Step 1) to the operator electrical box.
•
Secure using cable clamp on each end.
5) Join wires in cord from operator to wires in cord from junction box using wire nuts or
other suitable wire connectors.
6A) Non-Monitored sensing edge connects to terminal strip on main board
using (N-O REVERSE) terminals. See Fig. 10A.
6B) Monitored sensing edge connects to Timer-Close Module terminals (MON EDGE and GND)
or to (ODC STB) terminals on main board through a Miller Edge Interface Module
as shown in Fig. 10B.
Sensing Edge Installation
Figure 10B
NOTE:
:
2-wire Monitored
Sensing Edge
must be connected
through the MillerEdge
Interface Module.
NOTE: Monitored 2-wire
Sensing Edge can also
be used in combination
with a Timer-Close Module.
Figure 10A
NOTE
Non-monitored
Pneumatic or Electric Sensing
Edge can be connected
directly to these terminals.
DO NOT connect a 2-wire
Monitored Sensing Edge
to these terminals.
INTERFACE MODULE
NOTE: DO NOT USE TAKE UP REEL IF INSTALLING A 2 WIRE MONITORED EDGE.
SENSING EDGE
SENSING EDGE
SENSING EDGE
TIMER-CLOSE MODULE TERMINAL STRIP
MON
EDGE
GND
CONTROL SIGNAL TERMINAL STRIP
ODC
STB
ODC
STB
CONTROL SIGNAL TERMINAL STRIP
COIL TO
CONTROL
BOX
SENSING
EDGE
SENSING EDGE
ENCLOSURE
N-O
REVERSE
N-O
REVERSE
WARNING:
Actuating the operator using constant contact on the CLOSE
button will override non-functioning external reversing devices, including sensing edges.
AVERTISSEMENT:
L'activation de l'opérateur avec un contact
constant sur le bouton FERMER annulera les dispositifs de renversement externes non
fonctionnels, y compris les systèmes de détection des bords.
CONTINUED ON NEXT PAGE