Models FL3100H/3101H
21
North American Approved Applications:
The FAULT relay contact ratings are 8A @ 250
VAC and 8A @ 30 VDC.
European Union (EU) Approved Applications:
The FAULT relay contact ratings are 8A,
30 V RMS/42.4 V peak or 8A @ 30 VDC resistive max.
3.3.5 Alarm Reset Terminal
The RESET, when activated, returns a latched ALARM and/or WARN output that is no
longer valid, to its original state. For this RESET function, place one contact of a
normally open momentary switch to TB1 Terminal 3 and the other contact to DC COM
(the detector’s common). To activate, just press and release the switch.
TB1
Position
Relays
3 RESET
4
TEST
5 0-20
mA
Table 4: Alarm Reset Terminal Connections
By connecting one contact of a normally open, momentary switch, to TB1 Terminal 4
and the other contact to TB1 Terminals 9 and 10 (DC COM), the user can test the alarm
outputs of the flame detector by activating this switch for two to ten seconds depending
on the alarm time delay setting. The Alarm Test will activate the WARN and ALARM
relay outputs as well as the appropriate analog output. The flame detector will remain in
this state until the switch is released. Note: This function is also available via Modbus
and HART.
NOTE:
The latching WARN and/or ALARM will have to be RESET manually. The Alarm
Test feature
cannot
be daisy chained between two or more FL3100H/FL3101H
flame detectors.
Содержание FL3101H
Страница 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Страница 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Страница 24: ...17 Models FL3100H 3101H Figure 17 FL3100H FL3101H Field Terminations Figure 18 Detector Housing and Base ...
Страница 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Страница 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...