Models FL3100H/3101H
40
5.7.18 Remote Reset (11H)
Writing a 1 to the bit activates the Remote Reset function that resets the Alarm and Warn
Relays. The function is active momentarily and resets automatically after being used.
Function
Bit (LSB)
Access
Enable 1
Read/Write
Disable
0
Read/Write
Table 27: Remote Reset
EXCEPTION -
If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
5.7.19 Remote Alarm Test (12H)
Writing a 1 to the bit activates the Remote Alarm Test function, which activates the Warn and
Alarm relay and causes the Analog current to show warn then alarm. Once the Alarm Test is
complete, the Remote Alarm Test function should be disabled by writing a zero to the Remote
Alarm Test and then resetting the Alarm and Warn relays by writing a one to the Remote Reset
(referenced above).
Function
Bit (LSB)
Access
Enable 1
Read/Write
Disable
0
Read/Write
Table 28: Remote Alarm Test
EXCEPTION -
If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
5.7.20 Clear COPM Faults (13H)
Writing a 1 to the bit activates the Clear COPM Faults function that resets both the UV and IR
COPM faults. The function is active momentarily and resets automatically after being used.
Function
Bit (LSB)
Access
Enable 1
Read/Write
Disable
0
Read/Write
Table 29: Clear COPM Faults Function
EXCEPTION -
If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
5.7.21 Serial Number (15/16H)
The serial number is a 32-bit word but the value is only 23 bits long. The upper bits are always
zero. This is done to keep the same serial number as the HART serial number. Address 0x16
contains the lower part of the number and address 0X15 contains the upper part.
Содержание FL3101H
Страница 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Страница 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Страница 24: ...17 Models FL3100H 3101H Figure 17 FL3100H FL3101H Field Terminations Figure 18 Detector Housing and Base ...
Страница 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Страница 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...