Models FL3100H/3101H
44
NOTE
:
By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H / FL3101H Baud Rate will default to 19.2K.
5.7.42 Comm 2 Data Format (31H)
A read returns the Comm 2 data format of the FL3100H / FL3101H. A write changes the data
format to the requested data format. After the data format has been changed to the addressed
unit, the Modbus communications may cease or start producing Comm errors because the data
format has changed. Therefore, the master will have to change its data format to the slave’s
new data format in order to restart or provide proper communications.
Data
Parity
Stop
Format
Low Data
Byte
Access
8 None 1 8-N-1
00 Read/Write
8
Even
1
8-E-1
01
Read/Write
8 Odd 1 8-O-1
02 Read/Write
8
None
2
8-N-2
03
Read/Write
Table 31: Comm 2 Data Format
This function is indicated on the Low Data Byte (the High Data Byte is not used).
EXCEPTION -
If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
NOTE
:
By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H / FL3101H Data Format will default to 8-N-1.
5.7.43 Not Used (32H)
5.7.44 Input Voltage (33H)
A read returns the input voltage. This allows the user to remotely read the actual input voltage
via Modbus. If the measured voltage is below the required 20 volts measures should be taken
or low line faults may occur.
5.7.45 Alarm Test Voltage (34H)
This is useful if the Alarm test button is located a long distance from the FL3100H or the ground
is not a good ground. A read returns the Alarm input voltage. If the voltage is below 3.5 volts,
the Alarm test is activated.
5.7.46 Reset Relays Voltage (35H)
This is useful if the Reset test button is located a long distance from the FL3100H or the ground
is not a good ground. A read returns the Reset input voltage. If the voltage is below 3.5 volts,
the Reset is activated.
5.7.47 Dip Switch Settings (36H)
A read returns a digital copy of the dip switch. This is useful to check the FL3100H
configuration.
Содержание FL3101H
Страница 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Страница 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Страница 24: ...17 Models FL3100H 3101H Figure 17 FL3100H FL3101H Field Terminations Figure 18 Detector Housing and Base ...
Страница 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Страница 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...