Models FL3100H/3101H
39
EXCEPTION -
If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
NOTE
:
By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H, and FL3101H Baud Rate will default to 19.2K.
5.7.13 Comm 1 Data Format (0CH)
A read returns the Comm 1 data format of the FL3100H / FL3101H. A write changes the data
format to the requested data format. After the data format has been changed to the addressed
unit, the Modbus communications may cease or start producing Comm errors because the data
format has changed; therefore the master will have to change its data format to the slave’s new
data format in order to restart or provide proper communications.
Data
Parity
Stop
Format
Low Data
Byte
Access
8 None 1 8-N-1 00 Read/Write
8
Even
1
8-E-1
01
Read/Write
8 Odd 1
8-O-1 02 Read/Write
8
None
2
8-N-2
03
Read/Write
Table 26: Comm 1 Data Format
This function is indicated on the Low Data Byte and the High Data Byte is not used.
EXCEPTION -
If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
NOTE:
By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H, and FL3101H Data Format will default to 8-N-1.
5.7.14 UV Signal Count (0DH)
A read indicates the number of UV Signal Counts that have occurred within 500 ms, which is
the time duration that is required to detect a fire in the UV spectrum.
5.7.15 IR Signal Count (0EH)
A read indicates the number of IR Signal Counts that have occurred within 500 ms which is the
time duration that is required to detect a fire in the IR spectrum.
5.7.16 UV Fault Total (0FH)
A read indicates the total number of UV COPM Faults for an indefinite period of time until the
Clear COPM Fault command is activated. The maximum count is 65535 and then the counter
will rollover to zero and begin counting again.
5.7.17 IR Fault Total (10H)
A read indicates total number of IR COPM Faults for an indefinite period of time until the Clear
COPM Fault command is activated. The maximum count is 65535
and then the counter rolls
back to zero and begins counting again.
Содержание FL3101H
Страница 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Страница 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Страница 24: ...17 Models FL3100H 3101H Figure 17 FL3100H FL3101H Field Terminations Figure 18 Detector Housing and Base ...
Страница 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Страница 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...