Models FL3100H/3101H
47
6.0 Event Logging
6.1.1 Faults
Whenever the fault word changes, the time will be recorded.
The time of the fault will be saved.
The quantity of faults will be saved in a counter.
When the fault is removed, it is not saved and the counter is not incremented.
A fault event is logged for every 30 seconds recorded.
There are a total of 10 event time stamps stored.
6.1.2 Warning
At the time the fire level reaches the Warning level, the time is recorded. Each time this
happens a counter is incremented and saved. The end of the event is after the fire has
gone away and the latching state has been reset. There are a total of 10 event time
stamps stored.
6.1.3 Alarm
At the time the fire level reaches the Alarm level, the time is recorded. Each time this
happens a counter is incremented and saved. The end of the event is after the fire has
gone away and the latching state has been reset. There are a total of 10 event time
stamps stored.
6.1.4 Maintenance
At the time an alarm test occurs, the time is saved in the maintenance event log. Each
successful test increments and saves the maintenance counters. There are a total of 10
event time stamps stored.
6.1.5 Setting
Clock
Please see the table below.
Address
(hex)
Parameter
Function
Data Type
Data range
Access
40
Seconds Time Hi
Seconds Time Hi
Numeric value
0 – 65535
Timer Sec
41 Seconds
Time
Low
Seconds Time
Numeric value
0 – 65535
Timer Sec
42
Real Time Clock
Year, Month
Read/Set year and
month of RTC
2 Numeric
Values
0-99 year,
1 – 12 month
Timer Struct
43
Real Time Clock
Day, Hour
Read/Set day and
hour of RTC
2 Numeric
Values
1 – 31 day,
0 – 23 hour
44
Real Time Clock
Minute, Second
Read/Set minutes
and seconds of
RTC
2 Numeric
Values
0 – 59 minute,
0 – 59 second
Timer Struct
46
Event Index
Event index of
Logged Event
Numeric value
0 - 9
Index
47
Warn
Seconds Time Hi
for warning event
Numeric value
0 – 65535
Warn
Содержание FL3101H
Страница 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Страница 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Страница 24: ...17 Models FL3100H 3101H Figure 17 FL3100H FL3101H Field Terminations Figure 18 Detector Housing and Base ...
Страница 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...