7.3.4 TL105 UV/IR Test Lamp
The General Monitors TL105 Test Lamp is a battery operated, rechargeable test source
specifically designed to test General Monitors’ UV and UV/IR flame detectors.
It consists of a high-energy broadband radiation source, which emits sufficient energy in both
the Ultraviolet and Infrared spectra to activate UV and/or IR detectors. To simulate a fire, the
test lamp automatically flashes at the proper rate for different models. See TL105 instruction
manual.
The Model TL105, rated explosion-proof, is CSA certified for use in Class I, Groups C and D
areas.
The test lamp operates on internal batteries which, when fully charged, will operate
continuously for 30 minutes. An internal circuit will prevent operation when the batteries are
low.
7.3.5 TL105 Operating Instructions
It is always important to start a series of TL105 checks with a fully charged unit. Stand within 20
feet (FL3100H), 40 feet (FL3100H-Hydrogen), or within 35 feet (FL3101H) of the unit to be
tested and aim the TL105 squarely into the detector face. Shaking the lamp from side to side or
up and down will increase the simulation of flame flicker, and improve the response of the flame
detector to the lamp.
If the system is operating normally, the detector will go into a WARN condition after a few
flashes of the test lamp. If the lamp remains ON for the time-delayed period of the DIP switch
setting, the detector will go into ALARM.
To conserve charge, do not operate the test lamp longer than is necessary to test each
detector. When the battery level drops below the level required to maintain the proper intensity
of the lamp, an internal low voltage circuit will shut the lamp off until the batteries have been
recharged.
7.3.6 TL105 Recharging Instructions
Insert the charging plug into the receptacle. Complete recharging takes less than 2 hours
.
A
schedule of testing should be established and followed.
WARNING
: Replace the knurled plug after charging is complete. Charging must be carried
out in a non-hazardous area. The charging receptacle is located inside the
Содержание FL3101H
Страница 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Страница 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Страница 24: ...17 Models FL3100H 3101H Figure 17 FL3100H FL3101H Field Terminations Figure 18 Detector Housing and Base ...
Страница 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Страница 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...