Model 4802A
41
The Dust Guard is also available in a kit with twelve replaceable screens (Figure 68). It
can also be used as an effective windscreen, and is recommended for corrosive, windy
or high temperature environments.
Figure 68 – Dust Guard Assembly Kit Picture
6.2.5 Duct Mounting Plates
General Monitors produces a Duct Mounting Plate (P/N 10041) for applications that
require the sensor to be mounted in air-conditioning or heating duct. The Duct Mounting
Plate is easy to install (Figure 69).
Figure 69 – Duct Mounting Plate, Assembly Drawing
Read and understand the bulleted list below before mounting the Sensor into a duct.
•
Select a location on the duct and cut out a hole large enough for the Sensor to be
inserted into the duct.
•
Place the O-Ring over the Sensor threads, against the 1¼-inch hex on the wiring
side of the sensor.
•
Insert the wiring side of the Sensor through the Gasket and Cover.
•
Screw the Lock Nut onto the wiring side of Sensor.
•
Use the four screws to attach the mounted Sensor to the duct. The Sensor should be
oriented so that when the plate is attached to the duct the sensing element is inside
the duct.