Model 4802A
47
6.5 Electrical
Specifications
6.5.1 Input Power Requirement
20 to 35Vdc, (24Vdc @ 250mA, 4.8W nominal) (300 mA max).
PSU noise and ripple voltage 1.0Vpp max. The customer supplied PSU must comply
with IEC 1010-1, limiting current to 8A under Fault conditions, in order to comply with
CE Marking requirements.
6.5.2 Electrical Classification
The Sensor is rated for used in Class I, Division 1, Groups B, C & D or European Zones
1 & 2. The Model 4802A is designed for use in non-hazardous environments.
6.5.3 Relay Contact Rating
4A @ 30V RMS/42.4V PK, 3A @ 30VDC resistive. DPDT for A1 & A2, SPDT for Fault.
6.5.4 Open Collector Rating
100mA @ 35Vdc for A1, A2, Fault, UA, FUA, CAL-OC, LA1 & LA2.
6.5.5 Cable Parameters
Recommended 3-wire screened or screened and armoured per BS5308 or equivalent.
Maximum cable lengths allowable between module and sensor with one way resistance
of 5 Ohms per sensor lead (10 Ohms loop)
mm
2
AWG
Feet
Meters
2.5
14
7600 2320
1.5
16
4800 1460
1.0
18
3000 910
.75
20
1900 580
Figure 72 – Recommended Maximum Cable Lengths
Between Module & Sensor
The maximum allowable cable lengths between the analog output connections on the
control module with a remote device in series (maximum loop resistance of 500 Ohms
between AO+ & AO-):
mm
2
AWG
Feet
Meters
2.5
14
9000 2740
1.5
16
5200 1585
1.0
18
3800 1160
.75
20
2400 730
Figure 73 – Maximum Allowable Cable Lengths
Between Analog Output Connections On Control Module