Model 4802A
22
5.3 Calibration
Mode
To calibrate the Model 4802A, follow the procedure listed below:
1. Make sure the calibration gas is the same concentration as the user specified
calibration level.
2. Make sure the sensor is seeing clean air.
3. Place the cup from the portable purge calibrator over the sensor (Figure 41).
NOTE:
Do not attach cup from the portable purge calibrator over the sensor, until the
display shows “AC”.
Figure 41 – Portable Purge Calibrator
4. Enter the Calibration mode by following the procedure for entering the Calibration
Check mode, continuing to press and hold the Mode/Select switch until the
CAL
LED
turns on steady, about fifteen seconds (Figure 42).
Figure 42 – Entering CAL Mode