Model 4802A
35
Figure 62 – Entering A New Password
5.5 Inhibit
Mode
Whenever the
Inhibit
Mode is entered, the
A1
and
A2
alarm outputs are inhibited. The
front panel LED’s will still function normally in cases where sufficient gas is present at
the sensor. Once this mode has been entered, the user may exit the
Inhibit
Mode by
pressing the
Mode/Select
Switch.
NOTE:
- Before exiting Inhibit mode, remove gas from sensor and ensure sensor is
seeing clean air i.e. display shows zero.
NOTE -
Any latched alarms must be reset before exiting the
Inhibit
Mode.
There is a user selectable option that will place the unit in
Fault
every time the
Inhibit
Mode is entered. If the user does not select this option, the
Fault
circuit will function
normally during the
Inhibit
Mode.
While the unit is in the
Inhibit
Mode, the display will indicate
IN
for 5 seconds, then the
gas concentration will be displayed for 5 seconds. This sequence will repeat for as long
as the unit is in the
Inhibit
Mode.
The
Inhibit
Mode is provided so that the operation of the Model 4802A can be verified
without tripping external devices that are connected to the
A1
and
A2
alarm outputs.