Model 4802A
30
5.4.4 A1 Alarm Options
Next, the
A1
LED will be flashing while the Energized/De-energized option is displayed
(Figure 53). The display will indicate the current selection, (
En
or
dE
). Press the
Mode/Select
Switch to toggle the selection.
De-Energized
is the factory default for this
selection.
Figure 53 – A1 Energized-De-Energized Alarm Option
The
A1
LED on the front panel will be flashing while the latching/non-latching option is
displayed (Figure 54). The display will indicate the current selection, (
nL
or
LA
). Press
the
Mode/Select
Switch to toggle the selection.
Non-Latching
is the factory default for
this selection.
Figure 54 – A1 Latching/Non-Latching Alarm Option