Model 4802A
7
The Fault outputs are always normally energized when power is applied to the module.
The contact ratings for the A2 & A1 alarm and Fault relays are 4A @ 30V RMS/42.4V
Pk, 3A @ 30 VDC, Resistive, maximum.
Inductive loads (bells, buzzers, relays, etc.) on dry relay contacts must be clamped
down. Unclamped inductive loads can generate voltage spikes in excess of 1000 volts.
Spikes of this magnitude may cause false alarms and contact damage. Figure 27 shows
recommended relay protection circuits for AC and DC loads, respectively.
Figure 27 – Recommended Relay Protection Circuits
3.3.4 Other Open Collector Outputs
The terminal designation for the
Unaccept
and the Discrete
Calibration / Inhibit
Mode
outputs are:
Label
Term
Description
UA-OC
18d Unaccept
Output
CAL/INH
32z
CAL-Inhibit Mode Output
Figure 28 – Terminal Designations for
Unaccept and Calibration/Inhibit Mode
NOTE -
If the Backward Compatible configuration is ordered, the CAL/INH will not be
present (pin 32z will be for 0v).
The electrical rating for all open collector outputs is 100mA @ 35Vdc.