Quick Reference Guide
Installation Guidelines For 50 Hz Air-Cooled Generator Sets
47
Section 9: Quick Reference Guide
Quick Reference Guide
To clear an active alarm, press the OFF mode button and then the ENTER button on the control panel. Then press the
AUTO mode button. If the alarm reoccurs, contact an IASD.
Active Alarm
LED
Problem
Action
Solution
NONE
FLASHING
GREEN
Unit running in AUTO but
no power in house.
Check generator set
MLCB (generator set
disconnect).
Check generator set MLCB (generator set
disconnect). If it is ON, contact an IASD.
HIGH
TEMPERATURE
RED
Unit shuts down during
operation.
Check LEDs / screen
for alarms.
Inspect ventilation around generator set,
intake, exhaust, and rear of generator set. If
no obstructions are present, contact an
IASD.
OVERLOAD
REMOVE LOAD
RED
Unit shuts down during
operation.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from generator set. Put in AUTO and restart.
RPM SENSE
LOSS
RED
Unit was running and shut
down, attempts to restart.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from generator set. Put into AUTO and
restart. If generator set does not start,
contact an IASD.
NOT ACTIVATED
NONE
Unit will not start in AUTO
with mains power loss.
Verify if screen says
unit not activated.
See Activation section in owner’s manual.
NONE
GREEN
Unit will not start in AUTO
with mains power loss.
Check screen for start
delay countdown.
If startup delay is greater than expected,
contact an IASD to adjust from 2 to 1500
seconds.
LOW OIL
PRESSURE
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Check oil level and add oil as needed. If oil
level is correct, contact an IASD.
RPM SENSE
LOSS
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
option from MAIN MENU. If battery condition
displays GOOD, contact an IASD. If control
panel displays CHECK BATTERY, replace
battery.
OVERCRANK
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Verify fuel line shutoff valve is ON. Clear
alarm. Start unit in MANUAL. If it does not
start, or starts and runs rough, contact an
IASD.
LOW VOLTS
REMOVE LOAD
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from generator set. Put in AUTO and restart.
OVERSPEED
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
UNDERVOLTAGE
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
UNDERSPEED
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
STEPPER
OVERCURRENT
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
Содержание G007144
Страница 4: ...iv Installation Guidelines For 50 Hz Air Cooled Generator Sets...
Страница 56: ...Accessories 50 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 59: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 53 Wiring Diagram 10000007481 1 of 6...
Страница 60: ...Diagrams 54 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 2 of 6...
Страница 61: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 55 Wiring Diagram 10000007481 3 of 6...
Страница 62: ...Diagrams 56 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 4 of 6...
Страница 63: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 57 Wiring Diagram 10000007481 5 of 6...
Страница 64: ...Diagrams 58 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 6 of 6...
Страница 65: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 59 This page intentionally left blank...
Страница 66: ...Diagrams 60 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 67: ......