Troubleshooting
Installation Guidelines For 50 Hz Air-Cooled Generator Sets
45
Section 8: Troubleshooting
Generator Set Troubleshooting
Problem
Cause
Correction
Engine will not crank
Blown fuse.
Correct short circuit condition by replacing 7.5
amp fuse in generator set control panel. Con-
tact an IASD for assistance if fuse continues to
blow.
Loose, corroded, or faulty battery cables.
Tighten, clean, or replace as necessary.*
Faulty starter contact.
Faulty starter motor.
Discharged battery.
Charge or replace battery.
Engine cranks but will
not start
No fuel.
Replenish fuel / turn on fuel valve.
High fuel pressure.
Check and adjust fuel pressure.
Fuel selector in wrong position.
Set fuel conversion knob to correct position.
Faulty fuel solenoid (FS).
Contact an IASD for assistance.
Faulty spark plug(s).
Clean; inspect spark plug gap; replace spark
plug(s) as needed.
Valve clearance out of adjustment.
Reset valve clearance.
Engine starts hard and
runs rough
Air cleaner plugged or damaged.
Inspect and clean air cleaner.
Faulty spark plug(s).
Clean; inspect spark plug gap; replace spark
plug(s) as needed.
Incorrect fuel pressure.
Verify fuel pressure to regulator is 2.49–2.99
kPa (10–12 in water column) for LP gas, and
0.87–1.74 kPa (3.5–7 in water column) for NG.
Fuel selector in wrong position.
Set fuel conversion valve to correct position.
Valve(s) out of adjustment.
Adjust valve clearance.
Internal engine issue.
Contact an IASD for assistance.
Unit is set to OFF, but
engine continues to run
Controller wired incorrectly.
Contact an IASD for assistance.
Faulty control board.
No AC output from
generator set
Generator set MLCB (generator set
disconnect) is OFF (OPEN).
Set generator set MLCB (generator set
disconnect) to ON (CLOSED).
Generator internal failure.
Contact an IASD for assistance.
Engine may be warming up. See
Check controller screen to verify status.
Содержание G007144
Страница 4: ...iv Installation Guidelines For 50 Hz Air Cooled Generator Sets...
Страница 56: ...Accessories 50 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 59: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 53 Wiring Diagram 10000007481 1 of 6...
Страница 60: ...Diagrams 54 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 2 of 6...
Страница 61: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 55 Wiring Diagram 10000007481 3 of 6...
Страница 62: ...Diagrams 56 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 4 of 6...
Страница 63: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 57 Wiring Diagram 10000007481 5 of 6...
Страница 64: ...Diagrams 58 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 6 of 6...
Страница 65: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 59 This page intentionally left blank...
Страница 66: ...Diagrams 60 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 67: ......