Control Panel Startup / Testing
Installation Guidelines For 50 Hz Air-Cooled Generator Sets
37
Cold Smart Start
The Cold Smart Start feature is factory-enabled, and can
be disabled in the EDIT menu. Generator set will monitor
ambient temperature and adjust its warm-up delay
accordingly when Cold Smart Start is enabled. If ambient
temperature is below a fixed temperature upon startup in
AUTO mode (per chart below), generator set will warm
up for 30 seconds, allowing engine to warm before load
is applied. If ambient temperature is at or above fixed
temperature, generator set will start up with normal
warm-up delay of six seconds. See Cold Smart Start sec-
tion of the owner’s manual.
Cold Smart Start Set Point = 10 °C (50 °F)
Setting The Exercise Timer
This generator set is equipped with a configurable exer-
cise timer. There are two settings for the exercise timer:
•
Day/Time:
Generator set will start and exercise for
period defined, on day of the week and at time of
day specified. During this exercise period, unit runs
for five to twelve minutes depending on model, and
then shuts down.
•
Exercise frequency (how often exercise will
take place):
Can be set to Weekly, Biweekly, or
Monthly. If Monthly is selected, day of the month
must be selected from 1–28. Generator set will
exercise on that day each month. Transfer of loads
to generator output does not occur during exercise
cycle unless mains power is lost.
NOTE:
If installer tests generator set prior to installation,
press ENTER button to skip setting up exercise timer.
NOTE:
The exercise feature will operate only when gen-
erator set is placed in AUTO mode, and will not work
unless this procedure is performed. If Wi-Fi is not
enabled, current date/time must be reset every time
power is removed from the controller through the 7.5A
fuse and T1/T2 circuit and/or battery connections.
NOTE:
The exercise timer does not automatically adjust
for Daylight Saving Time.
NOTE:
When using the Wi-Fi module, exercise time will
be set at random. Time settings can be changed later.
See Wi-Fi manual for details.
Before Initial Startup
NOTE:
Unit has been run and tested at the factory prior
to being shipped and does not require any type of break-
in.
NOTE:
The unit comes from the factory filled with 5W-30
weight organic oil. Verify oil level and add appropriate vis-
cosity and amount of oil if necessary.
Activation is complete
when this screen is
displayed.
Follow controller
prompts to complete
installation.
Display Reads
Troubleshooting
Select Hour (0-23)
- 6 +
002231
ISO000135
Engine damage. Verify proper type and
quantity of oil prior to starting engine.
Failure to do so could result in engine
damage.
Wear ear protection.
ISO000107
ISO000537
Wear full eye protection and
protective clothing.
Содержание G007144
Страница 4: ...iv Installation Guidelines For 50 Hz Air Cooled Generator Sets...
Страница 56: ...Accessories 50 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 59: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 53 Wiring Diagram 10000007481 1 of 6...
Страница 60: ...Diagrams 54 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 2 of 6...
Страница 61: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 55 Wiring Diagram 10000007481 3 of 6...
Страница 62: ...Diagrams 56 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 4 of 6...
Страница 63: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 57 Wiring Diagram 10000007481 5 of 6...
Страница 64: ...Diagrams 58 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 6 of 6...
Страница 65: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 59 This page intentionally left blank...
Страница 66: ...Diagrams 60 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 67: ......