Generac Power Systems G007144 Скачать руководство пользователя страница 1

Installation Guidelines

50 Hz Air-Cooled Generator Sets

8 kVA to 13 kVA

Original Instructions

SAVE THIS MANUAL FOR FUTURE REFERENCE

Register your Generac product at:

www.activategen.com

1-262-953-5155

ISO000209b

This product is not intended to 
be used in a critical life support 
application.

Содержание G007144

Страница 1: ...rator Sets 8 kVA to 13 kVA Original Instructions SAVE THIS MANUAL FOR FUTURE REFERENCE Register your Generac product at www activategen com 1 262 953 5155 ISO000209b This product is not intended to be...

Страница 2: ...ps operating expenses at a minimum It is the operator s responsibility to perform all safety inspections to verify all maintenance for safe operation is performed promptly and to have the equipment in...

Страница 3: ...for Outdoor Noise Emission Directive 2000 14 EC ISO 8528 10 1998 Reciprocating internal combustion engine driven alternating current generating sets EN ISO 3744 2010 Determination of sound power leve...

Страница 4: ...iv Installation Guidelines For 50 Hz Air Cooled Generator Sets...

Страница 5: ...Generator Set Maintenance 18 Fresh Air for Ventilation and Cooling 18 Water Ingress Avoidance 18 Proximity to Utilities 18 Verify Wi Fi Range 18 Transportation Recommendations 19 Suitable Mounting Sur...

Страница 6: ...ical Checks 41 Generator Set Tests Under Load 41 Checking Automatic Operation 42 Installation Summary 42 Shutting Generator Set Down While Under Load Or During A Mains Power Outage 42 Section 8 Troubl...

Страница 7: ...TIONS for future reference This manual contains important instructions that must be fol lowed during placement operation and maintenance of the unit and its components Always supply this manual to any...

Страница 8: ...es negative battery cable D Fuel Selection Step 1 Unit set for Natural Gas NG operation Step 2 Press and rotate fuel selector 180 to change fuel type Step 3 Unit set for Liquid Propane LPG operation N...

Страница 9: ...the manual completely before installing or operating this equipment Do not smoke near this equipment Do not allow open flames near this equipment J Read Owner s Manual Read the manuals for an explana...

Страница 10: ...Safety Information 4 Installation Guidelines For 50 Hz Air Cooled Generator Sets Figure 1 1 Safety and Informational Decals A B C E F H J K G D L E M2 M1 P N Q K K...

Страница 11: ...llowing proper installation do nothing that might alter a safe installation and render the unit in noncompliance with locally applicable codes standards laws and regulations ISO000540 ISO000531a Follo...

Страница 12: ...is properly grounded before applying power ISO000218 Installation must comply with all national and local electrical building codes ISO000147 Unit must be positioned in a manner that prevents combust...

Страница 13: ...e atmospheres ISO000111 Keep clothing hair and appendages away from moving parts ISO000247a This unit is not intended for use as a prime power source It is intended for use as an intermediate power su...

Страница 14: ...228 Always recycle batteries at an official recycling center in accordance with all local laws and regulations ISO000548 Batteries emit explosive gases while charging Keep fire and spark away ISO00016...

Страница 15: ...or set shutdown procedure in Shut ting Generator Set Down While Under Load Or During A Mains Power Outage before opening the enclosure This allows adequate cooling to reduce the risk of exposure to ho...

Страница 16: ...al laws and standards the following publications may be used as a guide these apply to localities which recognize NFPA and ICC 1 National Fire Protection Association NFPA 70 The NATIONAL ELECTRIC CODE...

Страница 17: ...led damage is understood to mean dam age to contents of a package not evident at time of delivery but discovered later Required Tools General SAE and metric hand tools Wrenches Sockets Screwdrivers St...

Страница 18: ...enerator set lid 2 See Figure 2 4 Two locks A secure lid one on each side Press down on lid above side lock and unlock latch to correctly open lid Figure 2 4 Opening The Lid 3 Repeat for other side Li...

Страница 19: ...from enclosure before lifting up D Customer Connections and Loose Parts See Figure 2 7 and Figure 2 8 for customer connections and loose parts location Figure 2 10 illustrates parts shipped loose Figu...

Страница 20: ...to relevant specifications Indicator B Identifier Green means OFF OPEN Red means ON CLOSED Figure 2 9 Generator Set Main Line Circuit Breaker MLCB Parts Shipped Loose Figure 2 10 Parts Shipped Loose A...

Страница 21: ...nerator set exhaust contains carbon monoxide CO a poisonous potentially lethal gas that cannot be seen or smelled The generator set must be installed in a well ventilated area away from windows doors...

Страница 22: ...fresh air into the structure B Garage door CO can leak into garage if door is open or does not seal correctly when closed C Attic vent Attic vents ridge vents crawl space vents and soffit vents can a...

Страница 23: ...ront and ends of the generator set must be 0 91 m 3 ft This includes shrubs bushes and trees B Rear clearance Fuel and electrical connections are made here 457 mm 18 in minimum clearance per SwRI test...

Страница 24: ...re This includes trees shrubs and bushes Vegetation not in compliance with these clearance parameters could obstruct air flow In addition exhaust fumes from the gen erator set could inhibit plant grow...

Страница 25: ...ider B than the generator set on all sides Figure 3 4 Pea Gravel or Crushed Stone Concrete pads must be appropriately sized in accor dance with national state or local building codes Verify surface wh...

Страница 26: ...Site Selection and Preparation 20 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 27: ...ting device The unit is now ready to be lifted Generator Set Placement See Figure 4 3 All air cooled generator sets come with a composite pad The composite pad elevates the genera tor set and helps pr...

Страница 28: ...rator Sets Figure 4 4 Mounting Hole Location Three M10 or 3 8 in lag bolts not supplied are recom mended for securing generator set to a concrete pad NOTE The top of generator set carton has a templat...

Страница 29: ...ifica tion once the generator set is installed Always contact local fuel suppliers or fire marshal to ver ify codes and regulations for correct installation Local codes will mandate correct routing of...

Страница 30: ...as Propane 1 2 Load Full Load 1 2 Load Full Load 8 kVA 2 21 78 3 62 128 3 29 0 87 0 89 6 16 1 63 1 68 10 kVA 3 51 124 5 30 187 4 79 1 26 1 30 7 62 2 01 2 07 13 kVA 4 02 142 6 48 229 5 58 1 47 1 52 8 8...

Страница 31: ...B 3 2 in NFPA 54 or Table A 2 2 in the ICC IFGC Equivalent Lengths of Pipe Fittings and Valves for the correct values to be added to overall fuel piping length NOTE Pipe sizes are from the outlet of t...

Страница 32: ...optional accessory fuel shutoff valve permits making pressure checks for diagnostic purposes without going into the generator set enclosure Figure 5 4 Fuel Shutoff Valve with Manometer Port Flexible F...

Страница 33: ...cations contact local gas supplier 5 Close fuel valve when completed but keep man ometer connected for future tests of the generator set while starting running and under loads Performing Fuel System L...

Страница 34: ...e pressure port optional Must be located no more than 1 83 m 6 ft away from fuel inlet D Pipe fittings E Flexible fuel line F Verify clearance with gas provider Regulator should be a minimum of 1 5 m...

Страница 35: ...ated no more than 1 83 m 6 ft away from fuel inlet D Pipe fittings E Flexible fuel line F Verify minimum distance requirements for regulator vent according to local gas codes Regulator should be a min...

Страница 36: ...Fuel Conversion Gas Connections 30 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 37: ...or generator set control circuit wiring is prohibited Recommended wire gauge sizes for this wir ing depends on wire length as recommended in Table 6 3 Exception Conductors of AC and DC circuits rated...

Страница 38: ...onnections F Ground stud C1 Wire tie for sense wires E1 Power lug E1 G Protective earth PE ground lug Table 6 2 Customer Wiring Connections Terminal Numbering Decal Wire Numbers ORANGE YELLOW TAG N1 F...

Страница 39: ...er and in the Mobile Link Wi Fi app if used The controller is equipped with a common alarm relay providing contacts for an optional customer sup plied external alarm indicator The common alarm relay i...

Страница 40: ...y cables were factory connected at generator set Figure 6 2 Battery Cable Connections Proceed as follows to connect battery cables to battery posts 1 Connect red positive battery cable A from starter...

Страница 41: ...llow on screen instructions on the generator set along with Quick Start Guide supplied with the unit to connect generator set to home Wi Fi network 3 Wait for on line authentication of generator set a...

Страница 42: ...see Wi Fi manual If NO continue Press ENTER to begin the activation process If ESCAPE is pressed instead of ENTER the generator set will only run in manual mode for test purposes and NOT ACTIVATED is...

Страница 43: ...ill exercise on that day each month Transfer of loads to generator output does not occur during exercise cycle unless mains power is lost NOTE If installer tests generator set prior to installation pr...

Страница 44: ...ontrol panel for this test to be performed and pass NOTE All appropriate panels must be in place during any operation of generator set This includes operation by a servicing technician while conductin...

Страница 45: ...d DOWN arrows to select fuel type then press ENTER Fuel Selection NG or LP Follow setup process in Wi Fi manual Cold Smart Start YES or NO 006669 Default voltage 220V Use UP arrow to select output vol...

Страница 46: ...uring update process the Blue Manual light flashes then the Green Auto light flashes Sequence does this twice When update is complete the unit returns to Install Wizard menu When the controller powers...

Страница 47: ...itch terminal lugs where E1 and E2 wires are terminated Volt age should be the output voltage selected during installation 2V e g 218 222 VAC at a frequency of 49 5 50 5 Hz If voltage is incorrect ver...

Страница 48: ...switch 3 Turn on mains power supply to transfer switch using the means provided such as a mains MLCB NOTE Transfer switch will transfer to mains position 4 Set generator set MLCB generator set discon...

Страница 49: ...enerator set MLCB generator set disconnect to OFF OPEN 6 Remove 7 5 amp fuse from control panel To turn generator set back ON 1 Install 7 5 amp fuse in control panel 2 Verify generator set MLCB genera...

Страница 50: ...Control Panel Startup Testing 44 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 51: ...lace spark plug s as needed Valve clearance out of adjustment Reset valve clearance Engine starts hard and runs rough Air cleaner plugged or damaged Inspect and clean air cleaner Faulty spark plug s C...

Страница 52: ...ransfer relay circuit open Faulty control logic board Engine may be warming up See Cold Smart Start Check controller screen to verify status Unit consumes large amounts of oil Excessive engine oil Adj...

Страница 53: ...will not start in AUTO with mains power loss Check screen for start delay countdown If startup delay is greater than expected contact an IASD to adjust from 2 to 1500 seconds LOW OIL PRESSURE RED Unit...

Страница 54: ...isplays GOOD contact an IASD If control panel displays CHECK BATTERY replace battery BATTERY PROBLEM YELLOW Yellow LED illuminated in any state Check screen for additional information Contact an IASD...

Страница 55: ...a base wrap snaps together around the bottom of the new air cooled generator set This offers a sleek contoured appearance as well as offering protection from rodents reptiles and insects by covering t...

Страница 56: ...Accessories 50 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 57: ...CONTROL WIRING HOLE FOR 1 1 4 CONDUIT FUEL INLET 1 2 NPT 8 13kVA 3 4 NPT 20kVA REQUIRED FUEL PRESSURE NATURAL GAS 0 87 1 74 kPa 3 5 7 WATER COLUMN LIQUID PROPANE VAPOR 2 49 2 99 kPa 10 12 WATER COLUM...

Страница 58: ...GRAVEL PAD 127 5 0 914 36 0 MINIMUM OPEN AREA 914 36 0 MINIMUM OPEN AREA 457 18 0 MINIMUM OPEN AREA 914 36 0 MINIMUM OPEN AREA AIR OUTLET AIR INTAKE AIR INTAKE TOP VIEW FRONT VIEW RIGHT SIDE VIEW DO...

Страница 59: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 53 Wiring Diagram 10000007481 1 of 6...

Страница 60: ...Diagrams 54 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 2 of 6...

Страница 61: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 55 Wiring Diagram 10000007481 3 of 6...

Страница 62: ...Diagrams 56 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 4 of 6...

Страница 63: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 57 Wiring Diagram 10000007481 5 of 6...

Страница 64: ...Diagrams 58 Installation Guidelines For 50 Hz Air Cooled Generator Sets Wiring Diagram 10000007481 6 of 6...

Страница 65: ...Diagrams Installation Guidelines For 50 Hz Air Cooled Generator Sets 59 This page intentionally left blank...

Страница 66: ...Diagrams 60 Installation Guidelines For 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 67: ......

Страница 68: ...nc All rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S4...

Отзывы: