X
GEM-P3200 Programming Instructions
L
NAPCO Security Systems
WI818D 08/00
!
Page 50
⇐
!
1.
Select
the desired
zone option.
ZONE OPTIONS
50ms Loop Response
10ms Loop Response
Priority
Priority with Bypass
Auto-Bypass
!
2.
Enable
desired options
for each zone by drawing a
circle
"
around its
corresponding binary data
value.
NOTE:
No circle = feature disabled.
4
8
2
1
Draw Circle
ZN04 ZN03 ZN02 ZN01
!
3.
Search table
below
for data entry.
!
4.
Enter data
in address
locations (left and right digits).
NOTE:
Dark shaded data value box
shows option not available.
ADDRESS LOCATION
L
ADDR
R
blank (•) 1200
1
NOTE:
See Direct Address
Programming Example on
page 19.
4
8
2 1
DIGIT VALUE DATA ENTRY
Blank (
.
)
4
8
2 1
1
4
8
2 1
2
8
1
2
4
3
4
8
2 1
4
5
4
8
2 1
4
8
2 1
6
4
8
2 1
7
4 2 1
DIGIT VALUE DATA ENTRY
8
4 2 1
9
4 2 1
0
1
2
4
B
4 2 1
C
D
4 2 1
4 2 1
E
4 2 1
F
8
8
8
8
8
8
8
8
NOTES:
(A) 50ms & 20 ms Loop Response only available for zones 1-8.
(B) 2-wire Smoke Detectors only available for zones 7 and 8.
(C) If Fire Alarm Verification is selected, then Fire must also be selected.
DEFAULTS:
The zone options indicated are automatically set after exiting the Easy Menu Driven Mode.
!
Priority, Selective Bypass, Alarm Output, Auto Reset, Swinger Shutdown
,
Zone Area 1 and Zone Area 2
are enabled for the total number
of zones entered in
“AREA 1 # ZONES = 08” and “AREA 2 # ZONES = 00”
.
!
Alarm Telco 1
is enabled for all zones if [YES] is entered for “
REPORT ALL ZONES TO CENTRAL ZONES? Y/N
”.
!
Entry/Exit 1
and
Chime
are enabled for zone numbers entered in
“EXIT / ENTRY ZONES ”
.
!
Exit/Entry Follower
and
Interior Bypass
are enabled for zone numbers entered in
“INTERIOR ZONES”
.
!
Fire, Pulse Alarm Output and Fire Verification
is enabled for the zone numbers entered in
“FIRE ZONES”
.
!
2-Wire Smoke Detector is enabled for zone numbers entered in
“2 WIRE FIRE ZONES”
.
Note:
See “Number of Zones &
Keypads per Area” in Easy
Menu Driven program Mode.
ZONE OPTIONS / ZONES 1-48 (ADDRESS 1200-1786)
Zone
Options /
Zones
1-
48