L
NAPCO Security Systems
X
GEM-P3200 Programming Instructions
WI818D 8/00
!
Page 33
Direct Address Programming Example
Example:
Program Zones 6, 7 and 8 as Exit/Entry Follower Zones.
DETERMINE THE DATA ENTRIES
!
1. Referring to ZONE FEATURES in the Programming Worksheets that follow, Exit/Entry Follower for Zones 5
through 8 are located at address 1218, left digit. Circle
"
the data values for Zones 5–8.
!
2. Add the data values for Zones 6, 7 and 8: 2+4+8=14. From Tables 1 and 2, “14” (E) is entered as press
G4
. The right digit (for Zones 1 through 4, none of which are Exit/Entry Follower Zones) is entered as a
blank (•).
PROGRAM THE DATA ENTRIES
!
1. Enter the panel's Dealer Security Code (Address 0500), then press the
A
button.
!
2. Answer NO (
F
) to all questions until “
ACTIVATE PROGRAM Y/N
” is displayed; then press YES (
E
).
NOTE:
If you pass “
ACTIVATE PROGRAM
”, scroll backward using the the
B
button.
!
3. Press the
C
button to enter the Address Program Mode. Address "
0000
" will display.
!
4. Press
1 2 1 8
to access Address 1218.
The data for both digits will display and the cursor
will advance to the data field.
!
5. Press
G 4
to enter an “E” in the left digit and press
0
to enter a blank (•) in the right digit.
!
6. Press
J
to save.
ZONE OPTION
EXIT/ENTRY FOLLOWER
ZONES
LEFT DATA VALUES
SUM = 14 (CIRCLE
"
)
ZN08
ZN07
ZN06 ZN05
$
#
"
1
ADDRESS
1218
L
ADDR
R
E
1218
blank (•)
ZONES
RIGHT DATA VALUES
SUM = 0 (CIRCLE
"
)
ZN04
ZN03
ZN02 ZN01
8
4
2
1
ENTER DATA
"
Di
rec
t Addr
ess
Pr
ogr
am Mode
: Pr
ogrammi
ng Exa
m
ple