X
GEM-P3200 Programming Instructions
L
NAPCO Security Systems
WI818D 08/00
!
Page 22
B. GEM-RP3DGTL Keypad
Enter the Master Security Code (printed on microprocessor can) for a new panel or enter your custom
Dealer Program Code if programmed. Press
A
,
followed by NO (
F
) repeatedly until “17” is
displayed.
NOTE:
If you pass Function “17”, you can scroll back by pressing the
B
button. Press
YES (
E
) to enter the Dealer Program Mode. The GEM-RP3DGTL is a dual 7-segment digital
keypad. The questions will be in the form of a 2 digit number flashing in the digital display. Press the
A
button to
scroll through each segment.
Total Number of Zones in Area 1 & Area 2
(Appears for New Panel Only)
Directly enter the total number of zones to be programmed for Area 1 and
Area 2, respectively. Valid entries are from 01 to 48. Directly enter the total
number of zones, including leading zeros. Use number buttons
1
through
9
.
NOTE:
Press the
0
button for a zero. The system is
based on groups of 4 zones each (after the first 8 zones), and will
automatically round up to the next group of 4. For example, if you enter 18,
it will automatically convert this to 20 zones. Press
J
to save. Press NEXT
(
E
) button to proceed.
Note:
The GEM-P3200 is limited to a combined maximum of 48 zones and
7 keypads. All 48 zones and 7 keypads may be programmed in the EZ
Program Mode. For more options, see Zone and Keypad Options in Direct
Address Programming.
Fire Zones
(Appears for New Panel Only)
Enter the zone number of any Fire Zones (both 2-wire, 4-wire or wireless).
Valid entries are from 01 to 48. Directly enter each zone number, including
leading zeros, and press
J
to save, and then repeat for any additional
zone(s). Press NEXT (
E
) button to proceed.
NOTE:
If you are programming a 2 Area system, enter the zone number of
zones required for Areas 1 & 2. All fire zones are common to areas 1 and 2.
The Direct Address Program Mode can then be used to customize them as
needed. See Zone Options.
2-Wire Fire Zones
(Appears for New Panel Only)
Enter the zone number of any Fire Zones (from previous question) which
are to be used with 2-wire smoke detectors. The only valid entries are 07
and 08. Directly enter each zone number, including leading zeros. Press
J
to save, and then repeat for any additional zone.
NOTE:
Only zones
which have been designated as Fire Zones can be programmed as 2 Wire
Fire zones. Press NEXT (
E
) button to proceed.
NOTE:
JP7 must be set
to “2-WF” position for 2-wire fire zones 7 and 8 (refer to Installation
Instructions).
Local System or C.S. Reporting System
(Appears for New Panel Only)
Press YES (
E
) button for all zones to report; press NO (
F
) button
for no zones to report (LOCAL SYSTEM).
R
COMPUTERIZED SECURITY SYSTEM
ARMED
STATUS
SYSTEM ARMED
01/01/97 12:00AM
1 2
4
3
5 6
7 8 9 0
A
B
C
D
E
F
G
NEXT/YES
PRIOR/NO
AREA
GEMINI
ENT A1
1 7
INT ERIOR
BY PA SS
F IRE/T B L
SY S T BL
CHIM E
(Direct Entry)
04
INTERIOR
BYPASS
FIRE/TBL
SYS TBL
CHIME
INTERIOR
BYPASS
SYS TBL
CHIME
FIRE/TBL
(Direct Entry)
05
INTERIOR
BYPASS
FIRE/TBL
SYS TBL
CHIME
INTERIOR
BYPASS
SYS TBL
CHIME
FIRE/TBL
(Yes or No)
06
INTERIOR
BYPASS
FIRE/TBL
SYS TBL
CHIME
INTERIOR
BYPASS
SYS TBL
CHIME
FIRE/TBL
GEM-RP3DGTL Key
p
ad:
Zones
pe
r Area
, Fi
re
Zones, 2-Wire Fire Zones & CS Reporting
(Direct Entry)
01
INTERIOR
BYPASS
FIRE/TBL
SYS TBL
CHIME
INTERIOR
BYPASS
SYS TBL
CHIME
FIRE/TBL
(Direct Entry)
02
INTERIOR
BYPASS
FIRE/TBL
SYS TBL
CHIME
INTERIOR
BYPASS
SYS TBL
CHIME
FIRE/TBL
Flashing